Nordyne E3 user service a. Electrical Specifications, for Dual Circuit Installations

Models: E3

1 32
Download 32 pages 24.59 Kb
Page 22
Image 22
Table 9a. Electrical Specifications

Model

 

 

Maximum

Minimum

Copper Wire Size - See

Ground

Low

Supply

Total

Caution Below

Voltage

Number

Over-current

Circuit

Wire

Circuit

Amperes

60°C

90°C

Thermostat

E3E(*)

Rating

Ampacity

Size

 

 

(e.g., Romex)

(e.g., SEU)

Wire Size

 

 

 

 

 

 

-010H

Single

45.5

60

57

4

6

10

2-Wire system

 

Single

52.1

70

65

4

6

8

-012H

maximum wire

Dual "A"

28.0

40

35

8

8

10

lengths:

 

Dual "B"

24.2

30

30

10

10

10

 

24 Ga.= 55'

 

Single

66.3

90

83

2

4

8

-015H

22 Ga.= 90'

Dual "A"

45.5

60

56

4

6

10

20 Ga.= 140'

 

Dual "B"

20.8

30

26

10

10

10

 

18 Ga.= 225'

-017H

Single

71.3

90

89

2

4

8

 

Dual "A"

48.8

60

60

4

6

10

4 or more

 

Dual "B"

22.5

30

28

10

10

10

Wire systems

-020H

Single

87.1

125

109

0

2

6

maximum wire

Dual "A"

45.5

60

57

4

6

10

lengths:

 

Dual "B"

41.7

60

52

4

6

10

24 Ga.= 25'

 

Single

93.8

125

117

0

2

6

22 Ga.= 45'

-023H

Dual "A"

52.1

60

60

4

6

10

20 Ga.= 70'

 

Dual "B"

41.7

60

56

4

6

10

18 Ga= 110'

Model

 

 

Maximum

Minimum

Copper Wire Size - See

Ground

Low

Supply

Total

Caution Below

Voltage

Number

Over-current

Circuit

Wire

Circuit

Amperes

60°C

90°C

Thermostat

E3EX

Rating

Ampacity

Size

 

 

(e.g., Romex)

(e.g., SEU)

Wire Size

 

 

 

 

 

 

-010

Single

47.7

60

57

4

6

10

2-Wire system

-012

Single

54.3

70

67

4

6

8

maximum wire

Dual "A"

30.2

40

35

8

8

10

lengths:

 

Dual "B"

24.2

30

30

10

10

10

24 Ga.= 55'

 

Single

66.0

90

83

2

4

8

22 Ga.= 90'

-015

Dual "A"

46.0

60

57

4

6

10

20 Ga.= 140'

 

Dual "B"

20.0

30

25

10

10

10

18 Ga.= 225'

-017

Single

71.5

90

89

2

4

8

4 or more

Dual "A"

51.0

60

60

4

6

10

Wire systems

 

Dual "B"

22.5

30

28

10

10

10

maximum wire

-020

Single

86.0

125

109

0

2

6

lengths:

Dual "A"

46.0

60

57

4

6

10

24 Ga.= 25'

 

Dual "B"

40.0

60

50

4

6

10

22 Ga.= 45'

Replacement furnace for E2E(*)-015HB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E2E(*)-

Single

67.1

90

83

2

4

8

Replacement

Dual "A"

35.5

50

44

6

8

10

furnace for

015HBR

Dual "B"

31.7

40

39

8

8

10

E2E(*)-015HB

 

* Can be H or B

CAUTION: When sizing the wire, you must follow the guidelines of the latest revision of the NEC. NM-B wire is equivalent to “Romex” cable. SEU is equivalent to service entry cable. For NEC type NM-B wire, you must size the wire using 60C ratings per NEC article 326.

* Minimum overcurrent protection per NEC 424-3b not to be less than 125% of total amps for fi xed resistance heat.

Table 9a. Electrical Specifications

 

Circuit "A"

Circuit "B"

Model Number

Wire Gauge

 

Breaker

Wire Gauge

Breaker

E3E(*)

and Type

 

Size

and Type

Size

-012H

#8 NM-B

 

40 amp

#10 NM-B

30 amp

-015H

#6 SEU

 

60 amp

#10 NM-B

30 amp

-017H

#6 SEU

 

60 amp

#10 NM-B

30 amp

-020H

#6 SEU

 

60 amp

#6 SEU

60 amp

-023H

#6 SEU

 

60 amp

#6 SEU

60 amp

Replacement furnace for E2E(*)-015HB

 

 

 

E2E(*)-015HBR

#8 SEU

 

50 amp

#8 NM-B

40 amp

Table 9b. Recommended Electrical Application Guide

for Dual Circuit Installations**

**Alternate wiring combinations can be used. Refer to the latest revision of the NEC for these appropriate alternate combinations.

22

Page 22
Image 22
Nordyne E3 user service a. Electrical Specifications, for Dual Circuit Installations