II. SPECIFICATIONS

Enclosure Rating

• NEMA12 & 13 (equivalent to IP 52/54)

Operating Temperature

• Fluid: -20° to 240°F (-29° to 116°C)
• Ambient: -20° to 158°F (-29° to 70°C)

Environmental

• Humidity: 0–90 % non-condensing

Pressure (Aluminum / Brass Operating)

• Liquids (
1
/
4
" to 1-
1
/
2
"): 3500 psi (241 bar)
maximum, with a 3:1 safety factor
• Gases (
1
/
4
" to 1-
1
/
2
"): 1000 psi (82 bar)
maximum, with a 10:1 safety factor

Pressure (Stainless Steel Operating)

• Liquids (
1
/
4
" to
1
/
2
"): 6000 psi (414 bar)
maximum, with a 3:1 safety factor
• Liquids (
3
/
4
" to 1-
1
/
2
"): 5000 psi (345 bar)
maximum, with a 3:1 safety factor
• Gases (
1
/
4
" to 1-
1
/
2
"): 1500 psi (103 bar)
maximum, with a 10:1 safety factor

Accuracy

± 2% of full scale

Repeatability

± 0.5%

Pressure Drop

See Appendix for specific transmitter information

Electrical

Power Requirement:
• 0–5 Vdc Output 10-30 Vdc @ 0.75W maximum
• 0–10 Vdc Output 12-30 Vdc @ 0.75W maximum
• 4–20 mAOutput loop powered, 30 Vdc maximum
Power Consumption:
• 25 mAmaximum
Analog Outputs:
• 0–5 Vdc and 0–10 Vdc into 10,000 Ohms
minimum
• 4–20 mAinto 1000 Ohms maximum
(see Figure 2)
Circuit Protection:
• Reverse polarity and current limiting
Transmission Distance:
• 4–20 mAlimited by cable resistance
• 0–5 Vdc 1000 feet (300 m) maximum
• 0–10 Vdc 1000 feet (300 m) maximum
Isolation:
• Inherently isolated from the piping system

Rate and Totalization Display

• Fixed or toggle modes of operation for rate and
totalizer display
• 8 digit, .70" high numeric display for rate and
total
• 8 digit, .35" high alphanumeric display for units
and setup

Temperature Drift

• 50 ppm/ °C (Max)

Analog Output

• Resolution - 1:4000

Transient Over-Voltages:

• Category 3, in accordance with IEC 664

Pollution Degree:

• Category 2, in accordance with IEC 664
Additional dimension specifications can be found in
Table 1 on page 3.

FLR Flow Transmitter

Installation & Programming Instructions

Page 2

Figure 2. Load Limitations (4-20 mAOutput Only)