P00 | |
aux output | Remote |
function |
|
DOWN INC DEC | PORT |
P00 | |
genalert | 11.5vdc |
on setpoint |
|
DOWN INC DEC | PORT |
P00 | |
loadshed | 11.0 vdc |
off setpoint |
|
DOWN INC DEC | PORT |
P00 | |
ventfan | 13.0 vdc |
on setpoint |
|
DOWN INC DEC | PORT |
•From the Remote aux output function screen, press the <DOWN> soft key. This will bring up the first of several screen used to adjust which ever mode you have chosen for the AUX function.
•The genalert on setpoint functions are not available for
•The loadshed off setpointis the battery voltage which triggers the AUX to reduce the inverter and battery loads. When the battery voltage drops below this value for three seconds, the AUX powers a DC coil relay to disconnect an AC load. Once triggered, loadshed remains on for at least three minutes. The loadshed off setpointis adjustable from10
•When the AUX is set to ventfan, a fan ventilates a battery enclosure. The ventfan on setpoint establishes the battery voltage which energizes the AUX and thus the fan for a one minute period. The voltage setting has a range of 10.0
soft keys. Recharging causes batteries to emit mostly hydrogen gas; higher recharging voltages emit more gas. Press the <DOWN> soft key to view the ventfan off periodscreen.
21