LIST OF AUX FUNCTIONS
•Cool Fan activates the standard TurboFan which cools the FX.
•Divert DC and Divert AC allows the AUX to divert excess renewable energy to a DC or AC load, respectively. This allows control of energy sources such as wind turbines or
•AC Drop is activated when an AC power source disconnects from an FX. An indicator, such as an alarm, connected to the AUX warns a user that AC power is no longer available.
•Vent Fan provides 0.7 amps to run a 12 VDC fan for removing hydrogen from the battery compartment. Vent Fan can operate automatically when the VENTFAN ON voltage set point is exceeded or it can operate intermittently by adjusting the VENTFAN OFF PERIOD.
•In Fault mode, the AUX can send an alarm signal via radio, pager, or telephone device when the FX enters into an error condition. Fault mode can also be used to log error conditions by triggering an event recording device.
•GenAlert, through a 12VDC relay, will tell the system to start a
•Load Shed energizes the AUX the reduce the load demand on the batteries and the inverter function, thus acting as a load management system.
•Setting the AUX to Remote allows a message sent through the serial port on the MATE to switch the AUX on and off.
Note: Using Advanced Generator Start (AGS) overrides any programmed AUX function.
Adjustable AUX OUTPUT FUNCTIONS
There are four AUX functions whose settings can be adjusted by the user:
•Diversion
•Vent Fan
•GenAlert
•Load Shed
ADV/FX/AUX |
|
|
aux output | Remote | • From the Remote aux output function screen, press |
function |
| the <DOWN> soft key |
|
| |
DOWN INC | DEC PORT |
|
20