ADV/FX/AUX---------------

P00

ventfan off

5 min

period

 

DOWN INC DEC

PORT

ADV/FX/AUX---------------

P00

diversion

14.6 vdc

on setpoint

 

DOWN INC DEC

PORT

ADV/FX/AUX--------------

P00

diversion

30 sec

off delay

 

DOWN INC DEC

PORT

If a ventilation fan is only needed intermittently, the ventfan off periodshuts the fan off for a user- determined time before starting up again for a one- minute period when the battery voltage exceeds the ventfan on setpoint. This off period can be set from 0-30 minutes in one-minute increments using the <INC> and <DEC> soft keys. Setting this period to zero will keep the fan running the entire time the battery voltage is high enough to activate the ventfan function. Setting it to five minutes means the fan will run for one minute and then shut off for five minutes until the battery voltage drops and the fan is no longer needed. Press the <DOWN> soft key to view the diversion on setpoint screen.

After deciding on Divert DC or Divert AC, use the diversion on setpoint screen to choose the voltage which will activate this AUX OUTPUT FUNCTION. This value can range from 12.0 VDC-16.0 VDC and can be adjusted in 0.1 VDC increments using the <INC> and <DEC> soft keys. Press the <DOWN> soft key to view the diversion off delayscreen.

The diversion off relaydetermines how long the AUX will be energized after the battery voltage which caused the diversion falls below the diversion on setpoint. This delay can range from 0-240 seconds in one-second increments as adjusted with the <INC> and <DEC> soft keys.