STACKING INSTRUCTIONS
System Examples
STACKED SYSTEM USING OUTBACK’S “PARALLEL” STACKING
This type of system may have between 2 and 10 FX’s that will have their AC Outputs connected to the same Leg. We will be using a
In a quad stack, I am assuming that the top FX is plugged into port 1 of the HUB, the 2nd FX down is plugged into port 2, the 3rd FX down is plugged into port 3, and the 4th FX down is plugged into port 4 (This is not a rule, just for simplicity). Using the MATE, go to the stacking menu (explained earlier in the “Stacking Instructions” section). You are now at the 1st stacking menu called “Stack Phase”. In the upper right hand corner of the mate screen will always be the HUB port number of the FX you’re working with at the time. Let’s start out with the FX that’s on port 1. If something other than P01 appears in the upper right hand corner then press the PORT button until P01 appears. Set the “Stack Phase” of the port 1 FX to
Press the DOWN button 2 times to get into the “POWER SAVE LEVEL SLAVE ADJUST ONLY” menu. Press the PORT button until P02 is displayed in the upper right corner of the screen. This menu pertains to the slaves only which is why we’re starting out with port
2.The setting from the factory should be already set to 1 which is the 1st rank slave. If it’s anything other than 1, then press the INC or DEC buttons to make it 1. Press the PORT button to talk to the port 3 FX. Press the INC button to change the “power save level slave adjust only” to 2 which is the 2nd rank slave. Press the PORT button to talk to the port 4 FX. Press the INC button until the setting is 3 for 3rd rank slave. Now you’ve set the rank for all the slaves. If you have more FX’s in the system then press the PORT button to access the next FX and press INC until the number on the screen is 1 number less than the port number (i.e. if you are on P05, the number on the screen should be 4).
Let’s back track a little by going to the “POWER SAVE LEVEL MASTER ADJUST ONLY” menu. Do this by pressing the DOWN button, TOP button, then DOWN button. Verify that the screen you are on now is the “POWER SAVE LEVEL MASTER ADJUST ONLY” screen and change the port to P01. Turn on all of your FX’s AC Output breakers. The master FX’s “Inverter” LED should be solid and all the slaves “Inverter” LED’s should be blinking. Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” from 0 to 1 and watch the 1st slave’s “Inverter” LED go solid. When the “Inverter” LED is on solid, this means that the inverter is on. When the “Inverter” LED on the slave is blinking, this means the FX is asleep. Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” to 2 and watch the 2nd slave’s “Inverter” LED turn on. Adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” to 3 and watch the 3rd slave’s “Inverter” LED turn on. If you have more than three slaves then keep increasing the value in the “POWER SAVE LEVEL MASTER ADJUST ONLY” screen and verify that each slave’s “Inverter” LED comes on as expected. You have now verified that all FX’s are stacked correctly so adjust the “POWER SAVE LEVEL MASTER ADJUST ONLY” back down to 0 and have fun with your system!
3-PHASE STACKED SYSTEM (3 FX’S ONLY)
This type of system will include only three FX’s and must be set up as described here. Turn off all AC Output and AC Input breakers before powering up FX’s. In