RS232 Communications Protocol & Command Set (continued)

Request Input Voltage Level

Transmit the input AC voltage status

Send to UPS:

?INPUTVOLTS<CR>

Response from UPS:

XXX<SP>VAC<SP>IN<CR>

 

XXX is the input AC voltage represented

 

in ASCII.

Request Output Voltage Status

Transmit the output voltage state

Send to UPS:

?OUTPUTSTAT

Response from UPS:

XXX<SP>VAC<SP>OUT<CR>

 

XXX is the output voltage represented

 

in ASCII.

If the UPS is not in AVR or BATTERY mode:

Response from UPS: NORMAL<CR>

If the UPS is in AVR mode and boosting voltage by 13%

Response from UPS: AVRBOOST1<CR>

If the UPS is in AVR mode and boosting voltage by 26%

Response from UPS: AVRBOOST2<CR>

If the UPS is in AVR mode and bucking voltage by 11%

Response from UPS:

AVRBUCK1<CR>

If the UPS is in BATTERY mode

Response from UPS:

BATTERY<CR>

Request Load Level Status

Transmit the load level percentage.

Send to UPS:

?LOADSTAT<CR>

Response from UPS:

XX<SP>%LOAD<CR>

 

XX is the load percentage represented

 

in ASCII.

Request Battery Charge Level Status

Transmit the remaining battery charge percentage.

Send to UPS:

?BATTERYSTAT<CR>

Response from UPS:

XX<SP>%BATTERY<CR>

 

XX is the battery charge percentage

 

represented in ASCII.

Identify Equipment

Transmit the model number, firmware number and revision.

Send to UPS:

?ID<CR>

Response from UPS:

PANAMAX<CR>

 

M1500-UPS<CR>

 

FW<SP>PARTNUMBER<CR>

 

REV<SP>REVISION<CR>

List all Commands and Queries

 

 

Send to UPS:

HELP<CR>

Response from UPS:

MAIN_ON<CR>

 

MAIN_OFF<CR>

 

NCL_ON<CR>

NCL_OFF<CR>

BATTHRESH<CR>

BEEPON<CR>

BEEPOFF<CR>

RESTORE<CR>

?OUTLETSTAT<CR>

?INPUTVOLTS<CR>

?OUTPUTSTAT

?LOADSTAT<CR>

?BATTERYSTAT<CR>

?ID<CR>

HELP<CR>