RS232 Communications Protocol & Command Set

Communications Protocol

Baud rate:_______2400 bps

Stop bit:_______________1 bit

Start bit: ____________1 bit

Parity:________________None

Data length:_________8 bits

Flow control:____________one

 

 

Controller Commands

Commands and responses are in the form of ASCII character strings terminated with a carriage return <CR> ASCII character 13 (hex).

It is important to understand how the UPS circuitry switches power to the outlets in order to use the outlet switching commands effectively. The following diagram provides a basic illustration:

DB9 Pinout Diagram

5

4

3

2

1

6

 

7

8

9

PIN NO.

 

SIGNAL

 

1

 

 

-

 

2

 

TRANSMIT

3

 

RECEIVE

 

4

 

DTR

 

 

5

 

SIGNAL GROUND

6

 

 

-

 

7

 

RTS

 

 

8

 

 

-

 

9

 

 

-

 

DTR - Data Terminal Ready

RTS - Request To Send

AC INPUT/BATTERY

To Non-Critical Load (NCL) Outlets

MAINNCL

Figure 2.1 UPS Power Switching

To Critical Load (CL) Outlets

The UPS provides one bank of switched outlets (Outlet Bank 1) that can be controlled independently. These are referred to as Non-Critical Load (NCL) Outlets.

The other outlet bank (Outlet Bank 2) will be referred to as Critical Load (CL) Outlets.

Note that NCL outlets cannot be energized unless the critical load outlets are on.

NCL outlets are designated for equipment that is considered non-critical.

Power will be turned off if the battery charge falls below a set threshold (refer 2.5).

It is desirable to have the ability to switch the power to the outlets on and off to force a “hard” reboot of equipment. Devices such as satellite receivers often “crash” and must be reset.

The following are commands made by the controller to the UPS:

Main Power On

Send to UPS:

MAIN_ON<CR>

If power is not switched off due to low battery conditions:

Action:AC power is switched ON to the CL out lets by closing the AC input relay or turn ing on the inverter.

Response from UPS:

CL_OUTLETS_ON<CR>

 

NCL_OUTLETS_ON<CR> (if NCL relay is

 

closed)

If power is already switched off due to low battery conditions:

Action:None

Main Power Off

 

 

 

MAIN_OFF<CR>

Send to UPS:

Action:

All outlets are de-energized by discon-

 

 

necting the AC input relay and turning

 

 

off the Inverter.

Response from UPS:

NCL_OUTLETS_OFF<CR>

 

 

CL_OUTLETS_OFF<CR>

Response from UPS:

LOWBATT<CR>