( Continued from the previous page A. )

( Continued from the previous page B. )

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

Yes

 

 

 

Is the voltage of about DC22V to

 

 

 

 

 

 

24V given between the terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 and 3 on the indoor unit terminal strip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Serial Communication Line) ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Fig. 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Defect or connection error

 

 

 

 

 

Defect in the indoor unit

 

in the inter-unit cable

 

 

 

 

 

 

 

P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

1. Turn OFF the power and wait until the power lamp (LED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit controller is turned OFF.

 

 

 

 

1

2

 

3

4

5

6

 

2. Short-circuit between the terminals 2 and 3 on the outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit terminal strip.

(Fig. 3)

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

 

 

 

 

 

1.Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.

2.Perform the self-diagnosis five seconds after the operation start.

What is the latest self-diagnosis result ?

Condition: E01

Condition: E12

Indoor Unit

Fig. 3

Defect in the outdoor unit

P.C. board.

1.Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.

2.Remove the short-circuit between the terminals 2 and 3 on the outdoor unit terminal strip.

3.Disconnect the cable from the terminal 3 on the indoor unit

terminal strip.(Fig. 4)

Short-circuit between the terminals 2 and 3 on the indoor unit

terminal board.

(Fig. 5)

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

 

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 4

 

 

 

 

 

 

 

 

 

 

 

Fig. 5

 

 

 

 

 

1.Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.

2.Perform the self-diagnosis five seconds after the operation start.

Condition: E12

What is the latest self-diagnosis result ?Defect or connection error in the inter-unit cable

Condition: E01

Defect in the indoor unit

P.C. board

35

Page 35
Image 35
Panasonic R410A service manual From the previous page a

R410A specifications

Panasonic R410A is a refrigerant that has gained significant popularity in the air conditioning and refrigeration industry due to its favorable environmental properties and performance characteristics. Specifically designed to replace the harmful R22 refrigerant, which is being phased out due to its ozone-depleting potential, R410A offers a more eco-friendly alternative without compromising on efficiency or power.

One of the main features of R410A is its high energy efficiency. It operates at a higher pressure than R22, resulting in better heat transfer capabilities. This increased efficiency translates to lower energy consumption, making units using R410A more cost-effective in the long run. Additionally, R410A is known for its ability to provide excellent cooling performance even in high-temperature environments, making it suitable for a variety of applications, from residential air conditioning systems to commercial refrigeration units.

In terms of composition, R410A is a blend of two hydrofluorocarbons (HFCs), namely R32 and R125. This combination not only minimizes ozone depletion potential (ODP) but also reduces global warming potential (GWP) compared to older refrigerants. Panasonic has emphasized the importance of innovative technologies in its products, and R410A aligns perfectly with the company's commitment to developing sustainable solutions.

Panasonic also integrates advanced technologies to optimize the performance of R410A systems. For example, variable speed compressors, known as inverter technology, enhance system efficiency by adjusting the compressor's speed according to the cooling demand. This ensures that energy is only consumed when needed, further reducing operational costs.

Furthermore, R410A has a wide range of applications, including air conditioning systems, heat pumps, and chillers. Its versatility makes it a popular choice among manufacturers and consumers alike. The refrigerant is also compatible with existing R22 equipment, although specific retrofit procedures must be followed to ensure peak performance and reliability.

In conclusion, Panasonic R410A stands out as an innovative refrigerant choice in the HVAC industry, offering a combination of energy efficiency, environmentally friendly properties, and advanced technologies. As regulatory frameworks continue to tighten on greenhouse gas emissions, R410A and similar refrigerants are expected to play a crucial role in shaping a more sustainable future for air conditioning and refrigeration. Its high performance and lower environmental impact solidify its position as a leading refrigerant in contemporary cooling solutions.