VENTING, INLET AIR AND CONDENSATE
4.The minimum combined equivalent length is 16 equivalent feet.
5.The maximum combined equivalent length can be extended by increasing the diameter of the vent pipe. However, the transitions should begin a minimum of 15 equivalent feet from the boiler.
a.Transitions should always be made in vertical sections of pipe to prevent the condensate from pooling in the vent pipe.
b.Use a 3" x 2" reducing coupling to transition from the
c.Use a 4" x 3" reducing coupling to transition from the
d.The maximum equivalent length for the increased diameter vent pipes is 125 feet.
e.If the transition occurs at a distance greater than 15 equivalent feet from the boiler, the maximum equivalent length will be reduced. See Table 5.2. Standard Vent Pipe is 2” and Oversized Vent Pipe is 3” for
Table 5.2: Maximum Equivalent Vent Length for Oversized Vent Pipe
Transition | TEL of | TEL of | Maximum | |
Point | Standard 2” | Oversized 3” | ||
TEL of all | ||||
(ft from | or 3” Vent | or 4” Vent | ||
Vent Pipe (ft) | ||||
boiler) | Pipe (ft) | Pipe (ft) |
| |
|
|
|
| |
15 | 30 | 95 | 125 | |
|
|
|
| |
20 | 40 | |||
|
|
|
| |
25 | 50 | |||
|
|
|
| |
30 | 60 | 43 | 103 | |
|
|
|
| |
35 | 70 | 26 | 96 | |
|
|
|
| |
40 | 80 | |||
|
|
|
| |
None | 85 | 0 | 85 | |
|
|
|
|
TEL = Total Equivalent Length
E.EXHAUST VENT AND AIR INTAKE PIPE INSTALLATION
1.On the
2.On the
3.Use only solid PVC, CPVC, or ABS schedule 40 or 80 pipe. FOAM CORE PIPING IS NOT APPROVED.
4.Remove all burrs and debris from joints and fittings.
5.All joints must be properly cleaned, primed, and cemented. Use only cement and primer approved for use with the pipe material. Cement must conform to ASTM D2564 for PVC or CPVC pipe and ASTM D2235 for ABS pipe.
WARNING
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into the living space.
6.Horizontal lengths of exhaust vent must slope back towards the boiler not less than ¼" per foot to allow condensate to drain from the vent pipe. If the vent pipe must be piped around an obstacle that causes a low point in the pipe, a drain pipe must be connected to allow condensate to drain.
7.All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where condensate may form.
8.Do not use the boiler to support any piping.
9.A screened straight coupling is provided with the boiler for use as an outside exhaust termination.
10.A screened inlet air tee is provided with the boiler to be used as an outside intake termination.
11.The following are optional intake air/exhaust vent terminations available from your PB Heat, LLC distributor for use with Pinnacle boilers.
Table 5.3: Vent Termination Kits
| Stock |
Description | Code |
2" PVC Concentric Vent Termination Kit | 91469 |
|
|
3" PVC Concentric Vent Termination Kit | 91403 |
|
|
2" Stainless Steel Vent Termination Kit | 91465 |
|
|
3" Stainless Steel Vent Termination Kit | 91402 |
|
|
4" Stainless Steel Vent Termination Kit | 91401 |
|
|
12.Refer to Figure 5.3 to 5.10 for sidewall venting and Figures 5.11 to 5.14 for vertical venting.