PB Heat Gas Boiler manual Troubleshooting, Fault, Code, Description, Corrective Action

Models: Gas Boiler

1 47
Download 47 pages 37.42 Kb
Page 36
Image 36
Fault

TROUBLESHOOTING

Table 8.2: P125 Control Board Fault Codes

Fault

 

 

 

Code

Description

 

Corrective Action

 

 

 

 

 

 

1.

Check circulation pump operation.

 

 

2.

Assure that there is adequate flow through the boiler by accessing the status menu

 

 

 

and confirming that there is less than a 50°F rise from the return thermistor to the

 

 

 

supply thermistor.

F00

High Limit Exceeded.

3.

If gray thermostat wires are being used, disconnect them and jump them together.

 

If F00 code can be reset check thermostat circuit for short circuit or stray voltage.

 

 

 

 

 

4.

Check supply temperature reading on LED display. Replace High Limit Switch if

 

 

 

supply temperature is below 210°F.

 

 

5.

Temporarily jump out Water Pressure Switch. If F00 code can be reset check wiring

 

 

 

harness and connections. If wiring harness is okay replace Water Pressure Switch.

 

 

 

 

 

 

1.

Push the red reset button on the switch.

F01

Vent Temperature Limit Exceeded.

2.

Check the flue temperature during operation using a combustion analyzer.

 

 

3.

Replace the switch if faulty.

 

 

 

 

F02

Interrupted or Shorted

1.

Check the electrical connection to the thermistor on the outlet manifold.

Supply (Outlet) Thermistor.

2.

Replace thermistor if necessary.

 

 

 

 

 

F03

Interrupted or Shorted

1.

Check the electrical connection to the thermistor on the inlet manifold.

Return (Inlet) Thermistor.

2.

Replace thermistor if necessary.

 

 

 

 

 

 

 

1.

Check circulation pump operation.

F05

Supply (Outlet)

2.

Assure that there is adequate flow through the boiler by accessing the status menu

Temperature exceeded 230°F.

 

and confirming that there is less than a 50°F rise from the return thermistor to the

 

 

 

 

 

supply thermistor.

 

 

 

 

 

 

1.

Check circulation pump operation.

F06

Return (Inlet) Temperature

2.

Assure that there is adequate flow through the boiler by accessing the status menu

exceeded 230°F.

 

and confirming that there is less than a 50°F rise from the return thermistor to the

 

 

 

 

 

supply thermistor.

 

 

 

 

 

 

1.

Watch the igniter through the observation window provided.

 

No flame detected – The boiler will make three

2.

If there is no spark, check the spark electrode for the proper ¼" gap.

F09

attempts at ignition before the control goes into

3.

Remove any corrosion from the spark electrode.

 

this lockout condition.

4.

If there is a spark but no flame, check the gas supply to the boiler.

 

 

5.

If there is a flame, check the flame sensor.

 

 

 

 

 

 

1.

Check the gas pressure to the gas valve while the unit is in operation.

 

 

2.

Assure that the flame is stable when lit.

 

Loss of Flame Signal – The boiler will relight 4

3.

Check to see if the green light on the display module is out while the boiler

 

 

is running.

F10

times before the control goes into this lockout

 

4.

If the green light doesn't come on or goes off during operation check the flame

 

condition.

 

 

signal on the status menu.

 

 

 

 

 

5.

If the signal reads less than 1 microampere, clean the flame sensor.

 

 

6.

If the sensor continues to read low, replace it.

 

 

 

 

 

 

1.

Turn the gas off to the unit at the service valve.

 

 

2.

If the flame signal is still present replace the flame rod.

 

False Flame Signal – The boiler will lock out if

3.

If the flame signal is not present after turning off the gas supply, check

F11

it senses a flame signal when there should be

 

the gas valve electrical connection.

 

none present.

4.

If there is no power to the gas valve, remove the valve and check for obstruction

 

 

 

in the valve seat or replace the gas valve.

 

 

5.

Turn the gas on at the service valve after corrective action is taken.

 

 

 

 

 

Combustion Fan Speed Low – The boiler will

1.

Check the combustion air fan wiring.

F13

lock out if it senses that the fan speed is less than

2.

Replace the combustion air fan.

 

70% of expected for more than 60 seconds.

3.

Replace the control board.

 

 

 

 

 

Combustion Fan Speed High – The boiler will

1.

Check the combustion air fan wiring.

F14

lock out if the fan speed is more than 130% of

2.

Replace the combustion air fan.

 

expected for more than 60 seconds.

3.

Replace the control board.

 

 

 

 

 

 

1.

Make sure the connector is correctly connected to the gas valve.

F18

Gas Valve Error

2.

Check the electrical wiring from the valve to the control board.

3.

Replace the gas valve.

 

 

 

 

4.

Replace control board.

 

 

 

F30

Watchdog

Call factory for further assistance.

F31

Parameter Memory

Call factory for further assistance.

F32

Parameter Memory Write Error

Call factory for further assistance.

F33

Programming Error

Call factory for further assistance.

 

Neutral Fault – Boiler locks out if it senses

1.

Check for adequate supply voltage.

NC

a voltage drop or power feedback on the

2.

Check for power feedback on the neutral wire.

 

neutral wire.

 

 

 

 

 

 

 

34

Page 36
Image 36
PB Heat Gas Boiler manual Troubleshooting, Fault, Code, Description, Corrective Action