BOILER SET-UP

BOILER SET-UP

2. BOILER SET-UP

A.GENERAL

1.Pinnacle boilers are to be installed in an area with a floor drain or in a suitable drain pan. Do not install any boiler where leaks or relief valve discharge will cause property damage.

2.This boiler is not intended to support external piping. All venting and other piping should be supported independently of the boiler.

3.Install this boiler level to prevent condensate from backing up inside the boiler.

2. BOILER SET-UP CAUTION

This boiler is must be installed level to prevent condensate from backing up inside the boiler.

B.WALL HUNG BOILERS

1.The PI-T50 and PI-T80 Boilers are provided with slots for wall mounting and feet for floor mounting. Refer to Figure 10.1 in this manual for dimensions & locations.

2.If wall mounted, the boiler must be attached to a wall that provides adequate support for the boiler.

3.Use a minimum of 1/4" threaded fasteners for supporting the boiler. Do not mount the boiler to wall board only.

A.GENERAL WARNING

Make sure the boiler is adequately supported. Do not install this boiler on drywall unless adequately supported by wall studs.

4.Be sure to adequately support the boiler while installing external piping. Be sure to pipe condensate to a suitable drain or condensate pump.

C.FLOOR MOUNTED BOILERS

1.PI-80, PI-140, and PI-199 boilers are designed for floor mounting. The PI-80 can be wall mounted using the optional boiler stand available through your PB Heat, LLC distributor (Part Number 91439).

2.The boiler stand may used for floor mounting of the PI-140 and PI-199 boilers.