Unsupervised Alarms

Figure 18 illustrates the wiring configuration for supervised alarm inputs.

NORMALLY CLOSED

1K

1K

UNUSED

INPUTS

1 KMUST ALSO BE WIRED

NORMALLY OPEN

1K

1K

UNUSED

INPUTS

1 KMUST ALSO BE WIRED

Figure 18. Supervised Alarm Input Wiring

Unsupervised Alarms

When an alarm is configured as an unsupervised alarm, the NET5301T-I only triggers an alarm when the normal alarm state (open or closed) changes.

Figure 19 illustrates the alarm and no alarm conditions of an unsupervised alarm input. A normally closed alarm input can be defeated with a bypass. A normally open input can be defeated with a cut.

NORMALLY CLOSED

 

NORMALLY OPEN

 

NO ALARM

 

+V

NO ALARM

+V

GND

 

GND

ALARM

 

+V

ALARM

 

GND

 

GND

+V

ALARM

 

+V

NO ALARM

+V

GND

 

GND

NO ALARM

CUT

 

ALARM

CUT

GND

 

+V

GND

+V

 

BYPASS

 

BYPASS

 

Figure 19. Unsupervised Alarm Conditions

Figure 20 illustrates the wiring configuration for unsupervised alarm inputs.

NORMALLY CLOSED

NORMALLY OPEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNUSED INPUTS MAY BE SHORTED

UNUSED

INPUTS MUST BE LEFT UNWIRED

Figure 20. Unsupervised Alarm Input Wiring