Philips Electromagnetic Lamp manual 1 7 Watt losses

Models: Electromagnetic Lamp

1 48
Download 48 pages 10.2 Kb
Page 6
Image 6
 1  7  Watt losses

Manual background 5

1.6 Maximum coil temperature tw and ΔT

Another value marked on the ballast is the coil temperature rise Δt. This is the difference between the absolute coil temperature and the ambient temperature in standard conditions and is measured by a method specified in IEC Publ. 920 (EN 60920). Common values for Δt are from 50 to 70 degrees in steps of 5 degrees.

The coil temperature rise is measured by measuring the ohmic resistance of the cold and warm copper coil and using the formula:

 

Δt = {(R2 - R1)/R1} . (234.5 + t1) - (t2 - t1)

or:

tc = R2/R1 . (t1 + 234.5) - 234.5 (IEC 598-1 Appendix E)

where

R1

= initial cold coil resistance in ohm

 

R2

= warm coil resistance in ohm

 

t2

= ambient temperature at measuring R2 in Celsius

 

t1

= initial ambient temperature at measuring R1 in Celsius

 

tc

= calculated warm coil temperature in Celsius

 

Δt

= tc - t2 in Kelvin

The value 234.5 applies to copper wire; in case of aluminium wire, the value 229 should be used.

So a ballast marked with tw 130 and Δt 70, will have the specified 10 years average life in continuous operation at standard conditions at an ambient temperature of 130 - 70 = 60 ºC.When the ambient temperature around the ballast is higher, a shorter ballast life has to be accepted or sufficient air circulation or cooling has to be applied. The so-called ambient temperature mentioned in this chapter is not the room or outside temperature, but the temperature of the micro- environment of the ballast. Built into a luminaire or ballast box the air temperature around the ballast is higher than the outside ambient temperature.This higher temperature has to be added to the coil temperature rise Δt to find the absolute coil temperature: tc = t2 + Δt.

Additionally, a third temperature figure can be mentioned on the ballast: the ballast temperature rise in abnormal conditions, again measured according to specifications like EN 60920. In short: it is the winding temperature rise at 110 per cent mains voltage when the glow-switch starter, belonging to the system, is short-circuited.

The marking of the three temperature markings should be :

Δt ** / *** / tw *** with * = figure

Example: Δt 70 / 140 / tw 130.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background 1 Manual backgroundManual backgroundManual background 7 Manual background Watt losses

Ballast losses normally are published as ‘cold’ values, meaning that the ballast is not energised or only very shortly before and the ballast winding is at ambient temperature (25 ºC). In practice the ballast will reach more or less the marked Δt value and then the copper resistance is approx. 25 per cent higher than in the ‘cold’ situation.Therefore the ‘warm’ losses in practice will be 10 - 30 per cent higher than the published values.

112

Page 6
Image 6
Philips Electromagnetic Lamp manual 1 7 Watt losses