Sensaphone® ISACC Instruction Manual
VOICEThis keyword command allows you to select the input and output status infor mation to berecited when you call into the unit for a status report using a standard telephone.To display the infor mation to be recited during a voice status report, type show voice after anISACC prompt:
ISACC>show voice
VOICE STATUS SELECTION
IN01 = "LOW WELL FLOAT " = Yes
IN02 = "HI SUMP FLOAT " = Yes
IN03 = "Input #3 " = Yes
IN04 = "FLOW RATE (GPM) " = Yes
IN05 = "WELL LEVEL (FT) " = Yes
IN06 = "RESET " = Yes
IN07 = "Input #7 " = Yes
IN08 = "VOLTAGE " = Yes
IN09 = "Input #9 " = Yes
IN10 = "Input #10 " = Yes
IN11 = "Input #11 " = Yes
IN12 = "Input #12 " = Yes
IN13 = "Input #13 " = Yes
IN14 = "Input #14 " = Yes
IN15 = "Input #15 " = Yes
IN16 = "Input #16 " = Yes
OUT01 = "WATER PUMP RELAY" = Yes
OUT02 = "LOW WELL LIGHT " = Yes
OUT03 = "HI SUMP LIGHT " = Yes
OUT04 = "Output #4 " = Yes
OUT05 = "Output #5 " = Yes
OUT06 = "Output #6 " = Yes
OUT07 = "Output #7 " = Yes
OUT08 = "Output #8 " = Yes
OUT09 = "On board buzzer " = Yes
OUT10 = "On board relay " = Yes
OUT11 = "CONTROL VALVE " = Yes
OUT12 = "Analog output #2" = Yes
OUT13 = "Analog output #3" = Yes
OUT14 = "Analog output #4" = Yes
To prog ram the information to be provided in the voice status repor t, type set voice after anISACC prompt. At the prompt, enter Y to include the infor mation, or N to exclude. PressENTER to go to the next parameter:
ISACC>set voice
VOICE STATUS SELECTION
IN01 = "LOW WELL FLOAT " = Yes (Y or N) >
IN02 = "HI SUMP FLOAT " = Yes (Y or N) >
IN03 = "Input #3 " = Yes (Y or N) >
IN04 = "FLOW RATE (GPM) " = Yes (Y or N) >
IN05 = "WELL LEVEL (FT) " = Yes (Y or N) >
IN06 = "RESET " = Yes (Y or N) >
IN07 = "Input #7 " = Yes (Y or N) >N
IN08 = "VOLTAGE " = Yes (Y or N) >
IN09 = "Input #9 " = Yes (Y or N) >N
IN10 = "Input #10 " = Yes (Y or N) >N
IN11 = "Input #11 " = Yes (Y or N) >N