60
Sensaphone® ISACC Instruction Manual
LIMITS
ISACC allows you to set high and low limits for inputs defined as 4-20mA analog, 0-5V
analog, pulse count, temperature, table, or user defined. The limits are used to determine when
an input is in alarm. The command SET LIMITS prompts you to enter these values. NOTE:
An input defined as N.O. or N.C. does not have a high or low limit. ISACC will display N/A
for that input. An input defined as pulse count can only have a high limit.
To display the cur rent programmed limits, type show limits after an ISACC prompt. You
may display a specific limit by typing show limits followed by the input number.
ISACC>show limits
HIGH AND LOW ANALOG LIMITS
IN01 = "LOW WELL FLOAT " = N/A
IN02 = "HI SUMP FLOAT " = N/A
IN03 = "Input #3 " = N/A
IN04 = "FLOW RATE (GPM) " = LOW = -9999 HIGH = 9999
IN05 = "WELL LEVEL (FT) " = LOW = -9999 HIGH = 9999
IN06 = "RESET " = N/A
IN07 = "Input #7 " = N/A
IN08 = "VOLTAGE " = LOW = -9999 HIGH = 9999
IN09 = "Input #9 " = N/A
IN10 = "Input #10 " = N/A
IN11 = "Input #11 " = N/A
IN12 = "Input #12 " = N/A
IN13 = "Input #13 " = N/A
IN14 = "Input #14 " = N/A
IN15 = "Input #15 " = N/A
IN16 = "Input #16 " = N/A
To prog ram the low and high limits for analog or pulse count inputs, type set limits after an
ISACC prompt. Type a value and press ENTER to go to the next parameter. You may pro-
gram a specific limit by typing set limits followed by the input number.
ISACC>set limits
HIGH AND LOW ANALOG LIMITS
IN01 = "LOW WELL FLOAT " = N/A
IN02 = "HI SUMP FLOAT " = N/A
IN03 = "Input #3 " = N/A
IN04 = "FLOW RATE (GPM) " = LOW = -9999 >0001 HIGH = 9999 >0025
IN05 = "WELL LEVEL (FT) " = LOW = -9999 >0010 HIGH = 9999 >0150
IN06 = "RESET " = N/A
IN07 = "Input #7 " = N/A
IN08 = "VOLTAGE " = LOW = -9999 >0000 HIGH = 9999 >0110
IN09 = "Input #9 " = N/A
IN10 = "Input #10 " = N/A
IN11 = "Input #11 " = N/A
IN12 = "Input #12 " = N/A
IN13 = "Input #13 " = N/A
IN14 = "Input #14 " = N/A
IN15 = "Input #15 " = N/A
IN16 = "Input #16 " = N/A