Operation and Configuration

Standby Mode

When the UPS is turned off and plugged into a wall outlet or other power source, the UPS is in Standby mode. The battery recharges when necessary and the Power On indicator is off, indicating that power is not available from the rear receptacles.

How to Set DIP Switches

The DIP switches on the rear panel of each unit (see Figure 7) are used to configure the output voltage and utility power range.

1.The UPS must be completely shutdown.

Turn the UPS off by pressing the button on the front panel and then unplug the UPS.

2.Set the DIP switches according to the DIP switch configurations in Table 1.

3.Plug the UPS into a wall outlet or other power source and press the button to turn the UPS on.

UPS Rear Panel

DIP Switches

DIP Switch Detail 4 3 2 1

OFF

ON

Figure 7. DIP Switch Location

10

Powerware® 3115 User’s Guide S www.powerware.com