Specifications
Table 5. Electrical Output
| 120V Models | 230V Models | ||
|
|
| ||
Power Levels | PW3 300: 300 VA, 180W | PW3 300i: 300 VA, 180W | ||
(rated at nominal inputs) | PW3 420: | 420 VA, 252W | PW3 420i: | 420 VA, 252W |
| PW3 650: | 650 VA, 400W | PW3 650i: | 650 VA, 400W |
|
|
|
|
|
Regulation Online | Less than 1% of nominal input voltage loss from input to output at full load | |
Overload Protection | Online: 110 ±10% overload for 3 minutes; 120 ±10% overload for 10 cycles | |
| ||
|
|
|
Regulation | 120V default; 110, 120, 127V selectable | 230V default; 220, 230, 240V selectable |
(Nominal Voltage ±5%) |
|
|
|
| |
50/60 Hz ±1 Hz of nominal frequency | ||
Frequency |
|
|
|
| |
±5%, | ||
Regulation |
|
|
Step wave (synthesized sine wave) | ||
Form |
|
|
|
|
|
Overcurrent Protection | Online: resettable circuit breaker | Online: replaceable fuse |
| ||
| circuit protection | circuit protection |
|
|
|
Connections | PW3 300: Two | PW3 300i: Two |
| PW3 420: Two | PW3 420i: Two |
| PW3 650: Four | PW3 650i: Four |
|
|
|
Table 6. Battery
| 120V Models | 230V Models |
|
| |
Configuration | Internal batteries | |
Voltage | PW3 300: 1 each 12 Vdc battery | PW3 300i: 1 each 12 Vdc battery |
| PW3 420: 1 each 12 Vdc battery | PW3 420i: 1 each 12 Vdc battery |
| PW3 650: 2 each 6 Vdc batteries | PW3 650i: 2 each 6 Vdc batteries |
Type | Sealed, | |
Charging | 12 hours to 90% usable capacity at nominal line and no supplementary power supply load | |
Monitoring | Advanced monitoring for earlier failure detection and warning | |
Backup Time | PW3 300: 9 minutes | PW3 300i: 9 minutes |
(typical full load) | PW3 420: 5 minutes | PW3 420i: 5 minutes |
| PW3 650: 5 minutes | PW3 650i: 5 minutes |
Typical Life | Minimum 3 years float service life at ambient temperature | |
20 | Powerware® 3115 User’s Guide S www.powerware.com |