Specifications

Table 5. Electrical Output

 

120V Models

230V Models

 

 

 

Power Levels

PW3 300: 300 VA, 180W

PW3 300i: 300 VA, 180W

(rated at nominal inputs)

PW3 420:

420 VA, 252W

PW3 420i:

420 VA, 252W

 

PW3 650:

650 VA, 400W

PW3 650i:

650 VA, 400W

 

 

 

 

 

Regulation Online

Less than 1% of nominal input voltage loss from input to output at full load

Overload Protection

Online: 110 ±10% overload for 3 minutes; 120 ±10% overload for 10 cycles

 

On-Battery: 110 ±10% overload for 10 seconds; 120 ±10% overload for 1 second

 

 

 

Regulation On-Battery

120V default; 110, 120, 127V selectable

230V default; 220, 230, 240V selectable

(Nominal Voltage ±5%)

 

 

 

 

On-Battery Output

50/60 Hz ±1 Hz of nominal frequency

Frequency

 

 

 

 

On-Battery Voltage

±5%, -10% at low battery

Regulation

 

 

On-Battery Output Wave

Step wave (synthesized sine wave)

Form

 

 

 

 

 

Overcurrent Protection

Online: resettable circuit breaker

Online: replaceable fuse

 

On-Battery: active current limit and short

On-Battery: active current limit and short

 

circuit protection

circuit protection

 

 

 

Connections

PW3 300: Two 5-15 receptacles

PW3 300i: Two IEC-320 receptacles

 

PW3 420: Two 5-15 receptacles

PW3 420i: Two IEC-320 receptacles

 

PW3 650: Four 5-15 receptacles

PW3 650i: Four IEC-320 receptacles

 

 

 

Table 6. Battery

 

120V Models

230V Models

 

 

Configuration

Internal batteries

Voltage

PW3 300: 1 each 12 Vdc battery

PW3 300i: 1 each 12 Vdc battery

 

PW3 420: 1 each 12 Vdc battery

PW3 420i: 1 each 12 Vdc battery

 

PW3 650: 2 each 6 Vdc batteries

PW3 650i: 2 each 6 Vdc batteries

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

12 hours to 90% usable capacity at nominal line and no supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Backup Time

PW3 300: 9 minutes

PW3 300i: 9 minutes

(typical full load)

PW3 420: 5 minutes

PW3 420i: 5 minutes

 

PW3 650: 5 minutes

PW3 650i: 5 minutes

Typical Life

Minimum 3 years float service life at ambient temperature

20

Powerware® 3115 User’s Guide S www.powerware.com