C H A P T E R 5
SPECIFICATIONS
This section provides the following specifications for the
Powerware 3115 models:
SElectrical input and output
SBattery
SWeights and dimensions
SEnvironmental and safety
Table 3. Model List
| 120V Models | 230V Models |
|
|
|
UPS Models | PW3 300 | PW3 300i |
| PW3 420 | PW3 420i |
| PW3 650 | PW3 650i |
|
|
|
Table 4. Electrical Input
| 120V Models |
|
| 230V Models |
|
|
|
| |
Nominal Voltage | 120V default; 110, 120, 127V selectable |
| 230V default; 220, 230, 240V selectable | |
Power Factor |
|
| 0.6 |
|
Voltage Range |
|
| ||
| 88V - 142V |
|
| 166V - 260V |
| 93V - 142V |
|
| 176V - 260V |
| 98V - 142V |
|
| 186V - 260V |
| 103V - 142V (default) |
|
| 196V - 260V (default) |
Nominal Frequency |
| 50/60 Hz |
| |
Online Efficiency |
|
| 96% |
|
Noise Filtering |
| |||
Overcurrent | 10A, resettable circuit breaker |
| PW3 300i: | 3.15A fuse (12.6A fault current) |
Protection |
|
| PW3 420i: | 3.15A fuse (12.6A fault current) |
|
|
| PW3 650i: | 6.3A fuse (25.2A fault current) |
Connections | 10A, | |||
|
|
|
|
|
Powerware® 3115 User’s Guide S www.powerware.com | 19 |