Operation and Configuration

Table 1. DIP Switch Settings

120V Models

 

 

 

DIP Switch 1

DIP Switch 2

DIP Switch 3

DIP Switch 4

Output Voltage

110V

 

ON

OFF

 

 

 

 

 

 

 

 

 

120V*

OFF

OFF

 

 

 

 

 

 

 

 

 

 

127V

 

OFF

ON

 

 

 

 

 

 

 

 

 

Utility Power

103V

- 142V*

 

 

OFF

OFF

Range

 

 

 

 

 

 

98V - 142V

 

 

ON

ON

 

 

 

 

 

 

 

 

 

 

93V - 142V

 

 

OFF

ON

 

 

 

 

 

 

 

88V - 142V

 

 

ON

OFF

 

 

 

 

 

 

 

 

 

230V Models

 

 

 

 

 

DIP Switch 1

DIP Switch 2

DIP Switch 3

DIP Switch 4

 

 

 

 

 

 

 

Output Voltage

220V

 

ON

OFF

 

 

 

 

 

 

 

 

 

230V*

OFF

OFF

 

 

 

 

 

 

 

 

 

 

240V

 

OFF

ON

 

 

 

 

 

 

 

 

 

Utility Power

196V

- 260V*

 

 

OFF

OFF

Range

 

 

 

 

 

 

186V

- 260V

 

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

176V

- 260V

 

 

OFF

ON

 

 

 

 

 

 

 

 

166V

- 260V

 

 

ON

OFF

 

 

 

 

 

 

 

*Default position

 

 

 

 

 

 

Communication Port Configuration

To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. Use only the factory-supplied cable and software. See Table 2 for detailed information.

C A U T I O N

To prevent damage to your equipment, connect only a factory-supplied cable or a cable built to factory specifications (see Table 2) to the communication port. A standard serial cable may damage your computer.

Powerware® 3115 User’s Guide S www.powerware.com

11