Operation and Configuration

When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.

6 7 8 9

 

1

2

3

4

5

 

Figure 8. Communication Port

Table 2. Communication Port Configuration

 

 

 

 

 

 

 

 

Pin Number

Signal Type

 

Function

 

 

 

 

1

Input: RS-232 high level signal for >0.4

 

Conditional Power Off: In absence of AC power, output is

 

seconds

 

turned off until normal AC power returns

 

 

 

 

 

 

2Output: Open closing to logic ground pin 4 Impending Low Battery: Indicates the battery has less than 2 to 5 minutes of backup time left

3

Output: Open closing to logic ground pin 4

AC Input Failure: Indicates absence of normal AC input

4

Signal Return

Logic Ground

 

 

 

5

Output: RS-232 level low

Impending Low Battery: Indicates the battery has less than 2

 

 

to 5 minutes of backup time left

 

 

 

6

Output: RS-232 level high

AC Input Failure: Indicates absence of normal AC input

 

 

 

7

Not Used

Not Used

 

 

 

8

Not Used

Not Used

 

 

 

9

Chassis Ground (connected to pin 4)

Chassis Ground

 

 

 

12

Powerware® 3115 User’s Guide S www.powerware.com