16.The MIS and SLB breakers on the 80 kVA, 120 kVA, and 160 kVA UPS Sidecars are adjustable trip breakers and are set to maximum at the factory. During installation these breakers must be adjusted for the site requirements using the dial on each breaker. The MIS and SLB breakers on the 40 kVA UPS Sidecar are non-adjustable.

17.The continuous current (Ir) values for the corresponding lettered adjustment setting marked on the MIS and SLB breakers are listed in Table Q.

Table Q. MIS and SLB Continuous Current (Ir) Settings

Breaker

80 kVA Continuous

120 kVA Continuous

160 kVA Continuous

Setting

Current (Ir)

Current (Ir)

Current (Ir)

 

 

 

 

 

 

 

 

208V

480V

208V

480V

208V

480V

 

 

 

 

 

 

 

A

250

100

N/A

100

N/A

250

B

300

125

N/A

125

N/A

300

 

 

 

 

 

 

 

C

350

150

N/A

150

N/A

350

D

400

160

N/A

160

N/A

400

 

 

 

 

 

 

 

E

175

N/A

175

N/A

 

 

 

 

 

 

 

F

200

N/A

200

N/A

G

225

N/A

225

N/A

 

 

 

 

 

 

 

H

250

N/A

250

N/A

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

DRAWING NO:

164201546---4

 

SHEET:

10 of 10

 

 

 

 

 

REVISION: B

 

DATE:

063006

 

A-26

EATON Powerware® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com