Powerware Powerware 9390 manual Description Power Wiring Installation Notes

Models: Powerware 9390

1 124
Download 124 pages 14.91 Kb
Page 69
Image 69

INSTALLATION INFORMATION

Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 208V

 

 

 

 

 

 

 

 

 

 

 

Units

 

 

 

 

Rating 50/60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Unit Rating

 

 

 

 

 

 

 

 

 

UPS kVA

40

 

50

 

 

60

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

 

 

 

 

 

 

 

 

VOLTS

 

 

208

 

208

 

 

208

208

 

 

 

Output

 

 

 

 

 

 

 

 

 

VOLTS

 

 

208

 

208

 

 

208

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input from UPM

 

 

 

 

 

 

 

 

 

 

 

 

 

111

 

139

 

 

167

222

 

 

 

Full Load Current for each Module

 

 

 

 

 

 

 

 

 

AMPS

 

 

 

 

 

 

 

 

(3) Phases, (1) Neutral--- if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For customer-supplied wiring in a standalone

 

 

 

 

 

Minimum Conductor Size for each Module

 

 

 

 

 

 

 

installation, refer to the applicable Powerware 9390

 

 

 

 

 

 

 

 

installation and operation manual, listed in paragraph

 

Number per Phase for each Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5, for wire size. Wiring for line-up-and-match

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installation is factory-supplied.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

 

 

 

 

 

 

 

 

 

 

 

 

111

 

139

 

 

167

222

 

 

 

Full Load Current

 

 

 

 

 

D

 

 

 

AMPS

 

 

 

 

 

 

 

 

(3) Phases, (1) Neutral--- if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

AWG or kcmil

2/0

 

4/0

 

 

250

2/0

 

 

 

Number per Phase

 

 

 

 

 

 

 

 

 

(each)

 

 

(1)

 

(1)

 

 

(1)

(2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE Callout letter D maps to drawing 164201546 ---3, sheet 11 of 11.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for

 

 

 

 

 

 

 

Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 480V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units

 

 

 

 

 

 

 

Rating 50/60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Unit Rating

 

UPS

20

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(See

 

(See

 

40

 

50

 

60

80

 

100

 

120

 

160

 

 

 

 

kVA

 

 

 

 

 

 

 

 

 

 

 

 

Note 2)

 

Note 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

VOLTS

480

 

 

480

 

 

480

 

480

 

480

480

 

480

 

480

 

480

 

 

 

Output

 

VOLTS

480

 

 

480

 

 

480

 

480

 

480

480

 

480

 

480

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input from UPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current for each Module

 

AMPS

48

 

 

48

 

 

48

 

60

 

72

96

 

120

 

144

 

192

 

 

 

(3) Phases, (1) Neutral--- if required,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size for each

 

For customer-supplied wiring in a standalone installation, refer to the applicable

 

 

 

Module

 

Powerware 9390 installation and operation manual, listed in paragraph 1.5, for wire

 

 

Number per Phase for each Module

 

size. Wiring for line-up-and-match installation is factory-supplied.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

AMPS

48

 

 

48

 

 

48

 

60

 

72

96

 

120

 

144

 

192

 

 

 

(3) Phases, (1) Neutral--- if required,

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or

4

 

 

4

 

 

 

4

 

2

 

1

1/0

 

4/0

 

4/0

 

1/0

 

 

 

 

kcmil

 

 

 

 

 

 

 

 

 

 

 

 

 

Number per Phase

 

(1)

 

 

(1)

 

 

(1)

 

(1)

 

(1)

(1)

 

(1)

 

(1)

 

(2)

 

 

 

 

(each)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE 1. Callout letter D maps to drawing 164201546 ---3, sheet 11 of 11.

 

 

 

 

 

 

 

 

 

NOTE 2. 40/20 kVA and 40/30 kVA parallel systems must be wired same as a 40/40 kVA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

DRAWING NO:

164201546---4

 

 

 

 

 

SHEET:

3 of 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REVISION:

 

D

 

 

 

 

 

 

DATE: 092107

 

 

 

 

EATON Powerware® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com

A-19

Page 69
Image 69
Powerware Powerware 9390 manual Description Power Wiring Installation Notes

Powerware 9390 specifications

The Powerware 9390 is a high-performance uninterruptible power supply (UPS) that has been designed for mission-critical applications, providing reliable power protection and ensuring the continuous operation of sensitive equipment. It is particularly well-suited for data centers, telecommunications, and healthcare environments, where power reliability is paramount.

One of the standout features of the Powerware 9390 is its impressive scalability. This UPS is available in various capacities, typically ranging from 80 kVA to 500 kVA, allowing organizations to select a model that perfectly aligns with their power requirements. The modular design of the Powerware 9390 enables users to expand their system easily, accommodating future growth without significant investments in new equipment.

Another significant characteristic of the Powerware 9390 is its high efficiency. The UPS is equipped with advanced technologies that deliver exceptional energy efficiency, often exceeding 94% during normal operating conditions. This high efficiency not only reduces operational costs but also minimizes the carbon footprint of organizations, making the Powerware 9390 an environmentally friendly choice.

The unit offers advanced digital signal processing (DSP) technology, enhancing the unit's performance and ensuring that it can handle varying load conditions effectively. The Powerware 9390 is designed to provide a high level of protection against power disturbances and outages, including voltage sags, surges, and frequency variations.

The Powerware 9390 incorporates a user-friendly interface, featuring an intuitive LCD display that provides real-time information on system status, operational parameters, and alarms. This transparency allows facility managers to monitor the UPS at a glance and take necessary actions when required.

Additionally, for enhanced reliability, the Powerware 9390 supports a hot-swappable battery configuration. This feature is particularly beneficial as it enables battery replacement without disrupting the power supply, thus maintaining continuous operation during maintenance.

Moreover, the UPS supports various communication protocols, allowing integration with building management systems and enabling remote monitoring capabilities. This feature is crucial for operators who need to keep a constant eye on power conditions and ensure optimal performance.

In summary, the Powerware 9390 stands out as a robust, efficient, and scalable UPS solution. Its advanced technologies and features cater to the power protection needs of critical applications, making it an ideal choice for organizations that demand reliability and efficiency in their power systems. With its combination of scalability, energy efficiency, user-friendly interface, and robust protection capabilities, the Powerware 9390 continues to be a preferred solution for many industries worldwide.