INSTALLATION INFORMATION
1.The UPS Sidecar equipment operating environment must meet the weight requirements shown in the applicable Powerware 9390 installation and operation manual, listed in paragraph 1.5, plus 150 pounds for the UPS Sidecar. Size requirements are shown in Drawing
2.Do not tilt cabinets more than 10˚ during handling.
3.Dimensions are in millimeters (inches).
4.The clearances required around the UPS Sidecar cabinet are shown in Table A.
Table A. UPS Sidecar Clearances
From Top of Cabinet | Minimum clearance over the UPS Sidecar is |
| 457.2 mm (18”) for ventilation |
|
|
From Front of Cabinet | 914.4 mm (36”) working space |
|
|
From Back of Cabinet | None Required |
|
|
From Right Side of Cabinet | None Required |
5.The basic environmental requirements for operation of the UPS Sidecar are:
Ambient Temperature Range: | 40˚C | 104˚F) | |
Recommended Operating Range: | 25˚C | 77˚F) | |
Maximum Relative Humidity: | 95% noncondensing |