Powerware Powerware 9390 manual 25˚C, 164201546---2, 031505

Models: Powerware 9390

1 124
Download 124 pages 14.91 Kb
Page 55
Image 55

INSTALLATION INFORMATION

1.The UPS Sidecar equipment operating environment must meet the weight requirements shown in the applicable Powerware 9390 installation and operation manual, listed in paragraph 1.5, plus 150 pounds for the UPS Sidecar. Size requirements are shown in Drawing 164201546---8 starting on page A---68.

2.Do not tilt cabinets more than 10˚ during handling.

3.Dimensions are in millimeters (inches).

4.The clearances required around the UPS Sidecar cabinet are shown in Table A.

Table A. UPS Sidecar Clearances

From Top of Cabinet

Minimum clearance over the UPS Sidecar is

 

457.2 mm (18”) for ventilation

 

 

From Front of Cabinet

914.4 mm (36”) working space

 

 

From Back of Cabinet

None Required

 

 

From Right Side of Cabinet

None Required

5.The basic environmental requirements for operation of the UPS Sidecar are:

Ambient Temperature Range:

0---

40˚C (32---

104˚F)

Recommended Operating Range:

20---

25˚C (68---

77˚F)

Maximum Relative Humidity:

95% noncondensing

DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS

 

DRAWING NO:

164201546---2

 

 

SHEET: 1 of 1

 

REVISION:

A

DATE:

031505

 

 

 

 

 

 

EATON Powerware® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com

A-5

Page 55
Image 55
Powerware Powerware 9390 manual 25˚C, 164201546---2, 031505