4Termination Locations

A. Vent Termination Minimum Clearances

WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as specified.

Do not pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

Measure vertical clearances from this surface.

Measure horizontal clearances from this surface. (See Figure 4.4 for specific clearances.)

Figure 4.1 Termination Clearances

 

 

Gas or Wood

 

 

 

 

 

 

 

Termination

 

24 in. (610mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

 

 

(minimum) to

 

 

 

 

 

Perpendicular

 

 

 

 

Termination

 

 

Wall (Gas Only)

18 in.

 

 

(457mm)

 

 

HORIZONTAL

 

 

OVERHANG

2 FT.

2 FT.

 

MIN.

VERTICAL

 

 

LOWEST

WALL

 

 

 

DISCHARGE

 

 

OPENING

 

TERMINATION

 

 

CAP

 

 

 

 

X

 

 

12

 

 

ROOF PITCH

 

 

IS X/12

 

H (MIN.) - MINIMUM HEIGHT FROM ROOF

 

TO LOWEST DISCHARGE OPENING

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 6/12 to .......................................................7/12

1.25*

Over 7/12 to 8/12

1.5*

Over 8/12 to 9/12

2.0*

Over 9/12 to 10/12

2.5*

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

* 3 foot minimum in snow regions

Figure 4.3 Minimum Height from Roof to Lowest Discharge Opening

Figure 4.3 specifies minimum vent heights for various pitched roofs.

A

 

Gas Termination

Wood & Fuel Oil Termination

A

6 in. (152mm)

20 in. (508mm)

Figure 4.2 Multiple Vertical Termination

 

 

 

 

Page 8

Quadra-Fire · Topaz · 7009-113E

January 3, 2007

Page 8
Image 8
Quadra-Fire 839-1320, 839-1340, 839-1290, 844-4120 owner manual 4Termination Locations, Vent Termination Minimum Clearances