Isle Royale Wood Stove
SOLID PACK CHIMNEY WITH METAL SUPPORTS AS A THIMBLE
For the method of installation to a masonry chimney shown in Figures 12A & 12B, (page 12) it will be necessary to purchase a 12 inch (305mm) long 8 inch (203mm) inside diametert, section of prefabricated listed solid pack chimney to use as a thimble. Purchase a wall spacer, trim collar, and a wall band manufactured to fit the chimney section you purchase.
The safety features of this system are two fold: 1) a 2 inch (51mm) air space between the chimney section and combustible wall; and, 2) the 1 inch (25mm) air space around the chimney connector as it passes through the chimney section to the chimney.
The location of the opening through the wall to the chimney must leave a minimum 18 inches (457mm) vertical clearance between the connector pipe and the ceiling to prevent the ceiling from catching fire.
Measure as shown in Figure 11A. Cut an opening in the wall large enough to accommodate the outside dimension of the chimney section plus the minimum air space specified by its manufacturer. It may be necessary to cut the wall studs and install a header and a sill frame to maintain the wall support. The hole in the chimney must have at least an 8 inch (203mm) diameter fire clay liner or equivalent, secured with refractory mortar. If it is necessary to cut a hole in the chimney liner, use extreme care to keep it from shattering.
C
L
| FIRECLAY FLUE LINER |
CONCRETE CAP | WITH AIR SPACE |
|
Wall
Opening | Center of Hole |
Center Line
Center Line
Add the
| RAFTER |
| 1" (25mm) |
| CLEARANCE |
CEILING JOIST | WITH FIRESTOP |
| |
| COMBUSTIBLE WALL |
THIMBLE, |
|
12" (305mm) | |
OF BRICK |
|
FLOOR PROTECTOR |
|
FLASHING
EAVE
1" (25mm)
CLEARANCE
SHEATHING
AIRTIGHT CLEANOUT DOOR
Figure 11A
Figure 11B
WARNING! ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER’S INSTRUCTIONS FOR PROPER INSTALLATION.
CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING OR WALL, NEVER PASSING THROUGH A COMBUSTIBLE CEILING OR WALL. THE CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, OR A FLOOR, OR CEILING. MAINTAIN MINIMUM CLEARANCES TO COMBUSTIBLES AS REFERENCED ON PAGES 6,7.
|
|
|
|
February 4, 2005 | Page 11 |