Quadra-Fire installation instructions Isle Royale Wood Stove MOBILE HOME INSTALLATION

Models: Isle Royale

1 28
Download 28 pages 18 Kb
Page 15
Image 15
Isle Royale Wood Stove

R

Isle Royale Wood Stove

MOBILE HOME INSTALLATION

You must use a Quadra-Fire Outside Air Kit Part 831-1780 for installation in a mobile home.

1. An outside air inlet must be provided for combustion and must remain clear of leaves, debris, ice and/or snow. It must be unrestricted while stove is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a fire. Smoke spillage can also set off smoke alarms.

Spark Arestor Cap

2.Stove must be secured to the mobile home structure. Use 1/4 inch (6mm) lag bolts with the appropriate length for your installation to secure stove through pad and into floor.

3.Stove must be grounded with #8 solid copper grounding wire or equivalent and terminated at each end with N.E.C. approved grounding device.

4.Stove must be installed with an approved UL103 HT ventilated chimney connector, UL103 HT chimney, and terminal cap with spark arrestor. Never use a single wall connector (stove pipe) in a mobile home installation. Use only double-wall connector pipe, Dura-Vent DVL, Selkirk metalbestos DS, Security DL double wall connector or any listed double wall pipe connector.

5.Refer to page 6t of this manual or the Serial Number label on the back of the stove for clearances to combustibles.

Storm Collar

Joist Shield/Firestop

Floor Protector

Roof Flashing

WARNING: DO NOT INSTALL Listed Chimney Connector

Outside Air Kit Connector

6.Floor protections requirements on page 7 must be followed precisely.

Outside Air Floor Vent

7.In Canada, this appliance must be connected to a 6 inch (152mm) factory-built chimney conforming to CAN/ULC-629M, STANDARD FOR FACTORY BUILT CHIMNEYS. Floor protection referenced on page 7 must be followed.

8.Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure.

9.Follow the chimney and chimney connector manufacturer’s instructions when installing the flue system for use in a mobile home.

NOTE: Offsets from the vertical, not exceeding 45°, are allowed per Section 905(a) of the Uniform Mechanical Code (UMC). Offsets greater than 45° are considered horizontal and are also allowed, providing the horizontal run does not exceed 75% of the vertical height of the vent. Construction, clearance and termination must be in compliance with the UMC Table 9C. This installation also complies with NFPA 211.

WARNING: NEVER DRAW COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED. (i.e.,

DO NOT CUT THROUGH FLOOR JOIST, WALL STUD, CEILING TRUSS, ETC.)

WARNING: DO NOT INSTALL

IN SLEEPING ROOM.

NOTE: Top sections of chimney must be removable to allow maximum clearance of 13.5 ft. (411cm) from ground level for transportation purposes.

10. Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).

11 If unit burns poorly while exhaust blower is on in home, (i.e. kitchen range hood) increase combustion air.

 

 

 

 

February 4, 2005

250-5763B

Page 15

Page 15
Image 15
Quadra-Fire Isle Royale Wood Stove MOBILE HOME INSTALLATION, Warning Do Not Install In Sleeping Room