Quantum GAS-FIRED BOILERS Single Zone Boiler Piping, B.Pressure Relief Valve

Models: GAS-FIRED BOILERS

1 68
Download 68 pages 29.18 Kb
Page 18
Image 18
FIGURE 5 SINGLE ZONE BOILER PIPING

FIGURE 5 SINGLE ZONE BOILER PIPING

B.PRESSURE RELIEF VALVE

The boiler is furnished with a factory installed relief valve in the top of the boiler. Provide ¾” piping from the supplied relief valve to a local floor drain, but leave an air gap between piping and drain. No shutoff of any description shall be placed between safety relief valve and the boiler, or on the discharge pipes between such safety valve and the atmosphere. Installation of the safety relief valve shall conform to ANSI/ASME Boiler and Pressure Vessel Code, Section IV. The manufacturer is not responsible for any water damage.

C.EXPANSION TANK AND MAKE-UP WATER

Determine required system fill pressure, system design temperature, and system water content. Boiler contains 2.6 gallons (U.S.). Size expansion tank accordingly. Consult expansion tank manufacturer for proper sizing information. Connect properly sized expansion tank (not furnished) as shown in Fig. 6 for diaphragm type expansion tank and Fig. 7 for conventional closed type expansion tanks. For diaphragm type expansion tanks, adjust the tank air pressure to match the system fill pressure. Install air vent (furnished) as shown for diaphragm type expansion tank system only. Install make-up water connections as shown per local codes. If a pressure reducing valve is used, adjust to match the system fill pressure. In connecting the cold make-up water supply to the boiler, make sure that clean water supply is available. When the water supply is from a well or pump, sand strainer should be installed at the pump.

16

Page 18
Image 18
Quantum GAS-FIRED BOILERS Single Zone Boiler Piping, B.Pressure Relief Valve, C.Expansion Tank And Make-Upwater