SECTION C: COMBUSTION AND VENTILATION AIR
COMBUSTION AND VENTILATION AIR (Indoor Units)
The boiler must be supplied with sufficient quantities of
CAUTION:
NOTICE:
Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler and void the warranty. See appendix A.
It is recommended that the intake vent be insulated to minimize sweating.
DIRECT VENT-INSTALLATON
If outside air is drawn through the intake pipe directly to the unit for combustion:
1.Install combustion air direct vent in accordance with Section
2.Provide adequate ventilation.
3.In cold climates, and to mitigate potential
CONVENTIONAL COMBUSTION AIR SUPPLY (FOR U.S. INSTALLATION ONLY)
(a)All Air from Inside the Building. The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour (22 cm2 per kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (30 cm) of the top, and one opening shall commence within 12 inches (30 cm) of the bottom, of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (8 cm).
(b)All Air from Outdoors. The confined space shall communicate with the outdoors in accordance with methods 1 or 2. The minimum dimension of air openings shall not be less than 3 in. (8cm). Where ducts are used, they shall be of the same cross- sectional area as the free area of the openings to which they connect.
1.Two permanent openings, one commencing within 12in. (30cm) of the top, and one commencing within 12in. (30cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating with the outdoors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 sq in. per 4000 Btu per hr (5.5cm2 per kW) of total input rating of all equipment in the enclosure.
b. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 sq in. per 2000 Btu per hr (11 cm2 per kW) of total input rating of all equipment in the enclosure.
2.One permanent opening, commencing within 12 in. (30cm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16cm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 sq in. per 3000 Btu per hr (7 cm2 per kW) of the total input rating of all equipment located in the enclosure, and b. Not less than the sum of the areas of all vent connectors in the confined space.
WARNING:
Do not use one permanent opening method if the equipment room is under negative pressure condition or the equipment is common vented with other
11