SECTION J-5

SECTION J-5

Outdoor Installation

Outdoor models are self -venting when installed with the factory-supplied restricted direct vent cap and require no additional vent piping. This special vent cap is provided with the boiler in accordance with AGA/CGA requirements. It must be installed directly on the boiler. See Section B for correct clearances.

Care must be taken when locating the outdoor unit because the flue gases discharged from the vent hood can condense as they leave the hood. Improper location can result in damage to adjacent structures or building finish. For maximum efficiency and safety, the following precautions must be observed:

a)Outdoor models must be installed outdoors and must use the outdoor vent hood supplied by the manufacturer.

b)Periodically check venting system. The boiler’s venting areas must never be obstructed in any way and minimum clearances must be observed to prevent restriction of combustion and ventilation air. Keep area clear and free of combustible and flammable materials.

c)Do not locate adjacent to any window, door walkway, or gravity air intake. The vent must be located a minimum of four (4) feet horizontally, or four (4) feet below, or one (1) foot above such areas.

d)Install above grade level and above normal snow levels.

e)Vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.

f)Adjacent brick or masonry surfaces must be protected with a rust-resistant sheet metal plate.

g)Multiple Outdoor Vent installations require a four (4) feet clearance between vent caps.

NOTICE:

NOTICE:

Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.

On snow prone areas it is recommended that the combustion air terminal be located on the rear of the appliance to minimize snow blockage.

The restricted vent cap must be furnished by the boiler manufacturer in accordance with its listing.

An outdoor air filter, supplied by the manufacturer is mounted on the boiler.

HIDELTAOUTDOORVENTKITANDINSTRUCTIONS

NOTICE:

These instructions are intended for use by qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel are required to be licensed in some states. Persons not qualified shall not attempt repairs according to these instructions.

DANGER:

-SHOCKHAZARD

 

 

Make sure electrical power to the heater is disconnected to avoid damage to components, potential

 

 

serious personal injury or death. Make sure the gas to the heater has been shut off.

THISKITINCLUDES:

Vent Cap

 

1- Vent cap

8- Self tapping screws

 

1- Vent collar

4- Tinnerman clips

 

1- Collector

4- Screws

 

 