3.0START-UP

3.1Blower Adjustment

1.Disconnect all fan pressure switch tubings at plenum and connect manometer using a tee.

2.Close all manual firing valves.

3.Turn power on;

4.Check manometers attached to fan pressure switches. The readings should be 1.4 + .2"W.C. for propane and natural gas. If not, adjust the air shutter on the blowers to attain the correct value.

5.Turn power off.

6.Reconnect all fan pressure switch tubing to original positions.

3.2 Main Burner Adjustment

1.Turn off unit.

2.Open manual firing valves.

3.Turn on the unit, wait 15 seconds, and the igniter should glow. Sight glass to check ignitor at both ends of the boiler. Gas valves should be open after 45 seconds.

4.If burner does not light on first trial. It will retry, up to 3 times

5.Main burner ignition – check manifold gas pressure at gas valve outlet pressure tap. This should read 3.4 + .1"W.C. for natural gas and 10.5 + .1” W.C. for propane.

6.If the pressure reading differs by more than + .1"W.C. Remove screw cover off the gas pressure regulator, adjust main burner manifold pressure. Replace the screw cover of the gas regulator. Repeat step 2 – 5 on other valves as necessary.

Your Hi-Delta is tuned in!

3.4 Safety Inspection

Replace main gas manifold adjustment cap.

Check all thermostats and high limit settings.

During the following safety checks leave manometers hooked up, check and record.

If other gas fired equipment are in the room and on same gas main check all pressures on the Hi-Delta with all other equipment running.

Remember, incoming gas pressure could be lower than 7.0" W.C. for nat. gas and 11.0” W.C. for pro., provided 3.2.4 is met.

Check thermostats for ON/OFF operation.

Check Hi Limits for ON/OFF operation.

While in operation, check flow switch operation

Check the low gas pressure switches (For proper adjustment, if available, use the attached manometers to set pressure. The scales on the switch are approximately only ); Low gas pressure switch must be set at 5" W.C. for natural gas and 10.5” W.C. for propane.

High gas pressure switch (optional) at 1" W.C. above manifold pressure.

Insert ignition control lockout tests as safety check.

3.5 Follow-Up

Safety checks must be recorded as performed.

Turn unit on.

After main burner ignition.

Check Manometer for proper reading.

Cycle unit several times and recheck readings

Reanalyze with unit running record or print results.

Remove all Manometers and replace hose, remove jumper, replace all gas pressure caps.

Check for gas leaks one more time.

56

Page 56
Image 56
Raypak 302-902 manual Start-Up, Your Hi-Delta is tuned

302-902 specifications

The Raypak 302-902 is a highly efficient, reliable, and versatile heating solution commonly used in residential and commercial pool heating applications. Known for its exceptional performance and advanced technology, the Raypak 302-902 has become a favored choice among pool owners looking to extend their swimming season and enhance comfort.

One of the main features of the Raypak 302-902 is its robust construction. Built with a copper heat exchanger, it is designed to withstand the rigors of continuous use while offering superior heat transfer capabilities. The heat exchanger is also designed for easy maintenance, enabling pool owners to keep their systems running efficiently for years.

The Raypak 302-902 employs advanced digital controls, which provide precise temperature regulation. This modern control system allows users to set their desired water temperature with accuracy and maintain it consistently, ensuring a pleasant swimming experience. Additionally, these digital controls feature self-diagnostic capabilities, alerting users to potential issues, which aids in quick troubleshooting and maintenance.

In terms of energy efficiency, the Raypak 302-902 stands out with its ability to harness energy effectively, leading to significant savings in operational costs. It is equipped with an efficient gas burner, which optimizes fuel consumption while delivering rapid heating performance. This efficiency is complemented by its ability to operate with natural gas or propane, making it adaptable to various setups and preferences.

The unit also prides itself on its environmentally friendly operation. It meets stringent regulations for emissions, ensuring that pool owners can enjoy a pool heating solution that is both effective and reduces its ecological footprint. This focus on sustainability has made it a popular choice among environmentally conscious consumers.

Moreover, the Raypak 302-902 is designed for versatility. It can be easily integrated with existing pool systems and is compatible with both in-ground and above-ground pools. This flexibility allows it to cater to a wide range of pool sizes and configurations, making it suitable for both residential and commercial applications.

In conclusion, the Raypak 302-902 offers an array of features, technologies, and characteristics that make it a top contender in the pool heating market. With its durable construction, advanced digital controls, energy efficiency, and environmentally friendly operation, it remains a reliable choice for those seeking comfort and convenience in their swimming experience. Whether for a backyard oasis or a commercial facility, the Raypak 302-902 delivers consistent performance and accessibility.