SECTION I: ELECTRICAL POWER CONNECTIONS

SECTION I: ELECTRICAL POWER CONNECTIONS

Installations must follow these codes:

·National Electrical Code and any other national, state, provincial or local codes or regulations having jurisdiction.

·Safety wiring must be N.E.C. Class 1.

·Boiler must be electrically grounded as required by N.E.C. ANSI/NFPA 70-latest edition.

·In Canada, C.S.A. C22. 1 C.E.C. Part 1.

The boiler is wired for 120 Volts, 12 AMPS. The voltage is indicated on the tie-in leads. Consult the wiring diagram shipped with the boiler in the instruction packet. The remote tank control stat, thermostat, or electronic boiler control as applicable, may be connected to the stage selector terminal (See wiring diagram). 24 Volts are supplied to this connection through the boiler transformer. DO NOT attach line voltage to the “TH” leads. Before starting the boiler check to insure proper voltage to the boiler and pump.

FIELD-CONNECTEDCONTROLLERS

If unit does not have a factory wired stage controller, the unit is factory-wired in On/Off configuration with other stage terminals jumpered.

To field-connect stage controller, remove fac- tory-installed jumper and wire stage control as shown.

 

ON/OFF

 

Stage Selector

Factory

Stage 2

Jumpered

Control

Stage 1

 

2-STAGE

 

Stage Selector

Control

Stage 2

Stage 2

 

Control

Stage 1

Stage 1

 

Install a separate disconnect means for each load. Use appropriate-sized wire as defined by NEC, CSA and/or local code. All primary wiring should be 125% of minimum rating.

It is strongly recommended that all individually-powered control modules and the boiler should be supplied from the same power source.

SURGE PROTECTION

Microprocessor-based and solid state controls are vulnerable to damage from voltage and amperage fluctuations in the power supply. All sensitive control components should be protected by a suitable commercial-grade surge protection device.

If any of the original wire as supplied with the boiler must be replaced, it must be replaced with 105°C wire or its equivalent.

CHECK THE POWER SOURCE

WARNING:

Using a volt-ohm meter (VOM), check the following voltages at the circuit breaker panel prior to connecting any equipment: Make sure proper polarity is followed and house ground is proven.

FIGURE I-1

CHECK POWER SOURCE

AC = 108 VoltsAC Minimum, 132 VoltsAC MAX AB = 108 VoltsAC Minimum, 132 VoltsAC MAX

BLACK CIRCUIT

BREAKER

WHITE

GREEN

GROUND

A B C

VOLT-OHM

METER

Fig. # 9237