IGNITION CONTROL MODULE

IGNITION CONTROL MODULE

 

The intermittent ignition device conserves energy by automatically extinguishing

 

the pilot when the desired temperature is reached. When additional heat is needed,

 

the combustion air blower starts to purge all air from the combustion chamber for

 

about 45 seconds. On proof of air flow, the air proving switch closes and the pilot

 

reignites electrically, eliminating the fuel costs of maintaining a constant pilot. To

 

assure safe operation, the gas valve cannot open until the pilot relights and is

 

verified. The 100% pilot safety is an electronic device which closes the main gas

 

valve within 8/10 of a second whenever the pilot flame is interrupted. Pilot flame is

 

automatically lit when the device is powered and pre-purged. Unit performs its own

IGNITION MODULE

safety check and opens the main valve only after the pilot is proven to be lit.

HIGH LIMIT - MANUAL RESET

 

This appliance is equipped with a manual reset, high limit, safety device. Push the

 

reset button and adjust the setting to 40°F above the desired operating temperature.

 

MANUAL RESET HIGH LIMIT

FLOW SWITCH

Dual-purpose control shuts off boiler in case of pump failure or low water condi- tion. Mounted and wired in series with the main gas valve. Check with Manufac- turer for proper paddle size. Utilize correct paddle size for proper operation.

NOTICE:

Flow switch will not operate if flow is less than 20 GPM.

FLOW SWITCH

HIGH LIMIT - AUTO RESET

This appliance is equipped with an automatic, high limit, safety device. Set the auto high limit to 30°F above the desired operating temperature.

AUTO RESET HIGH LIMIT

54