IGNITION CONTROL MODULE |
|
The intermittent ignition device conserves energy by automatically extinguishing |
|
the pilot when the desired temperature is reached. When additional heat is needed, |
|
the combustion air blower starts to purge all air from the combustion chamber for |
|
about 45 seconds. On proof of air flow, the air proving switch closes and the pilot |
|
reignites electrically, eliminating the fuel costs of maintaining a constant pilot. To |
|
assure safe operation, the gas valve cannot open until the pilot relights and is |
|
verified. The 100% pilot safety is an electronic device which closes the main gas |
|
valve within 8/10 of a second whenever the pilot flame is interrupted. Pilot flame is |
|
automatically lit when the device is powered and | IGNITION MODULE |
safety check and opens the main valve only after the pilot is proven to be lit. | |
HIGH LIMIT - MANUAL RESET |
|
This appliance is equipped with a manual reset, high limit, safety device. Push the |
|
reset button and adjust the setting to 40°F above the desired operating temperature. |
|
MANUAL RESET HIGH LIMIT
FLOW SWITCH
NOTICE:
Flow switch will not operate if flow is less than 20 GPM.
FLOW SWITCH
HIGH LIMIT - AUTO RESET
This appliance is equipped with an automatic, high limit, safety device. Set the auto high limit to 30°F above the desired operating temperature.
AUTO RESET HIGH LIMIT