SECTION O: ADB INITIAL START-UP
1.0TOOLS NEEDED
•One
•Three
•“T” fitting
•7/16” and 1/2" open end wrenches
•Small and large
•Volt meter
•Amp probe
•Elec. Dual reading thermometer with strap on sensors
•3/16” Allen wrench
•Remote switch with 12" minimum lead wires (“Monkey” switch)
•Combustion analyzer
2.0 PREPARATION FOR
WARNING:
DO NOT TURN ON GAS AT THIS TIME
2.1Check Power Supply
With volt meter at incoming power check voltage between:
Hot - Common | (approx 120 VAC) |
Hot - Ground | (approx 120 VAC) |
Common - Ground | (< 1 VAC) |
If Common - Ground is > 1 VAC - STOP: Contact electrician to correct ground failure. Warning: Failure to do this may burn out
2.2 Attach Manometers to Measure Pressures (See Figure:
•Attach 16" scale manometer to the first main gas
•Attach one 8" scale manometer to the outlet side of the second main gas
(2).
•Attach one 8" scale manometer to the outlet side of pilot gas valve pressure tapping, Location (3).
•Attach one 8" manometer to "T" fitting, air pressure switch, and aluminum tubing, Location (4).
Turn Off Main Gas Valve;
Turn Off Pilot Gas Valve;
Reset Low Gas Pressure
2.3 Bleed Air from Gas Line
CAUTION: Make sure there is no ignition source in the boiler room
•With power off, slightly open union outside the cabinet to bleed air.
•Close union when you smell gas.
•Wait minimum 5 minutes to clear the gas out of the boiler room before continuing.
59