![SECTION P: POST START-UP CHECK](/images/new-backgrounds/35648/35648123x1.webp)
SECTION P: POST START-UP CHECK
Check off steps as completed:
1.Boiler and heat distribution units or storage tank filled with water?
2.Automatic air vent, if used, open two full turns during venting procedure?
3.Air purged from system?
4.Air purged from gas piping? Piping checked for leaks?
5.Followed
6.Is burner flame visible?
7.Test safety controls: If boiler is equipped with a low water cutoff or additional safety controls, test for operation as outlined by manufacturer. Burner should be operating and should go off when controls are tested. When safety devices are restored, burners should reignite after
8.Test limit control: While burner is operating, move indicator on high limit control below actual boiler water temperature. Burner should go off while blower circulator continues to operate. Raise setting on limit control above boiler water temperature and burner should reignite after
9.Test ignition system safety device:
•Turn power off.
•Close the pilot manual valve.
•Turn power on; after about 45 seconds of
•Turn the power off; open the pilot manual valve; (reset the lockout module if applicable).
•Wait 30 seconds, then turn power on. The burner should ignite after
10.To restart system, follow lighting instructions in Section O.
11.High limit control set to design temperature requirements of system? For multiple zones: flow adjusted as required in each zone?
12.Boiler cycled with thermostat? Raise to highest setting and verify boiler goes through normal
13.Observed several operating cycles for proper operation?
14.Set room thermostat or tankstat to desired temperature?
15.Reviewed all instructions shipped with this boiler with owner or maintenance personnel, returned to envelope and given to owner or placed in pocket inside front panel on boiler?
EMISSIONS GUIDELINES:
General guidelines for flue gas analysis for the ADB boilers:
Emissions will vary with different applications (hydronic, water heater, or pool), venting (including direct vent), ambient conditions (T, P, and humidity), and the condition of the boiler.
Emissions:
Gas | Range |
CO2 | |
CO | |
NOx | |
O2 |
62