Regency C33-NG2, C33-LP2 Test For Flue Spillage, Log Set Installation, Valve Description, Diagram

Models: C33-LP2 C33-NG2

1 24
Download 24 pages 6.96 Kb
Page 11
Image 11
Valve Description

INSTALLATION

Valve Description

1)Gas cock knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection

5)Main Operator

6)Outlet Pressure Tap

7)Inlet Pressure Tap

8)Pilot Outlet

9)Main Gas Outlet

10)Flange Securing Screw Holes

11)Alternative TC Connection Point

12)Thermoelectric Unit

13)Additional Valve Mounting Hole

1)Start all exhaust fans in the home and then close all doors and windows in the room.

2)Light the unit and set controls to maximum.

3)After five minutes, test that there is a “pull” on the flue by placing a smoke match, cigarette or similar device which gives off smoke, on the edge of the draft hood. See Diagram below.

The smoke should be drawn into the draft hood. If the smoke is still not drawn into the draft hood, turn the unit off and check for the cause of the lack of draft. If necessary, seek expert advice.

Note: If the flue is blocked or has a strong reverse flow, the thermally actuat- ed safety switch mounted in the draft hood will automatically shut off the gas supply in less than 10 minutes. If the heater turns off because of this during the spillage test, check for the cause of the lack of draft and if necessary, seek expert advice.

To reset the thermally actuated safety switch, let the unit cool for 10 minutes, then press the red reset button on the back of the switch. See Diagram below.

The gas log kit contains the following:

a)Front Log

b)Rear Log

c)Small Cross Logs (2)

d)Bag of embers

e)Bag of rock wool

1)Remove the logs from the box and carefully unwrap them. The logs are fragile, handle with care. Do not force into position.

2)Place the rear deflector on the rear log support pins in the back of the unit.

3)Place the rear log into the rear of the firebox, aligning the holes on the underside of the log with the rear log support pins and carefully push the log down onto the pins. See diagrams 1 and 2.

4)Ensure the front deflector is over front log pins. See diagram 1.

5)Place the front log in the front of the unit, aligning the holes on the underside of the log with the log support pins in the front of the unit. Carefully push the log down onto the pins. See diagram 1.

TEST FOR FLUE

SPILLAGE

Diagram 1

6)Place the cross logs on top of the larger logs aligning the holes on the underside of the cross log with the log pins in the larger logs. See diagrams 1 & 2. Carefully push the cross logs onto the pins.

This heater must be properly connected to a venting system.

WARNING: Operation of this heater when not connected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.

A “spillage” test must be made before the installed unit is left with the customer. Follow the procedure below:

LOG SET

INSTALLATION

WARNING: Dangerous operating conditions may occur if these logs are not positioned in their approved locations. Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot and burner operation.

Diagram 2

7)Distribute the embers along the mesh em- ber tray, but do not cover the burner ports. (Burner ports are the little holes on the top of the burner tube.) Pull off ember size pieces from the rock wool. Gently place the pieces on top of the embers. See diagram 3.