GAS PRESSURE TEST

INSTALLATION

The Regency Insert incorporates its own inter- nal draft hood, so no additional external draft hood is required. Periodically check that the vent is unrestricted

and an adequate draft is present

when the unit is in operation. (See page

9 for spillage test.)

Before installing vent system ensure that the damper plate is locked into the open position and secure to prevent the damper plate from falling down and crushing the liner.

GAS PRESSURE TEST

The unit is preset to give the correct gas input at the specified manifold pressures shown on the label. The maximum gas manifold pressure is:

Natural Gas:

3.8" w.c.

Propane

11" w.c.

The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point. The pres- sure check should be carried out with the unit burning and the setting should be with in the

limits specified.

Note: Use the same manner to check the inlet pressure.

AERATION SYSTEM

The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude.

Natural Gas:

3/16" open

Propane:

1/2" open

The aeration adjustment gears are located on the right side of the burner box and can be accessed from the side or from the front when the louvers are removed.

To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shutter. Open the air shutter for a blue flame or close it for a yellower flame.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air shutter is closed too much.

Note: Any damage due to carboning re- sulting from improperly setting the aeration controls is NOT cov- ered under warranty.

Note: Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installation or service.

TEST FOR FLUE

SPILLAGE

A “spillage” test must be made before the installed unit is left with the customer. Follow the procedure below:

1)Start all exhaust fans in the home and then close all doors and windows in the room.

2)Light the unit and set controls to maximum. Turn fan off.

3)After five minutes, test that there is a “pull” on the flue by placing a smoke match, cigarette or similar device which gives off smoke, in front of the spill tube. To ensure a valid test, place a scrap piece of sheet metal (or other non-combustible material) between the spill tube and the upper lou- ver, this will prevent the natural convection of the unit from interfering with the test. See diagrams below.

normal draft

downdraft or

 

blocked flue

Spill T ube

Non-combustible

Scrap

The smoke should be drawn into the spill tube, if it does not, leave the unit for a further five minutes and retest as above. If the smoke is still not drawn into the spill tube, turn the unit off and check for the cause of the lack of draft. If necessary, seek expert advice.

For wind turbulent sites, a wind cap may remedy the problem.

Note: The thermally activated safety switch will sense the change in