Regency Wraps F33 Gas Connection, System Data, Valve Description, Gas Pipe Pressure Testing

Models: F33

1 28
Download 28 pages 1.38 Kb
Page 9
Image 9
GAS CONNECTION

INSTALLATION

GAS CONNECTION

The gas connection is a 1/2 inch BSP Male thread. The gas line can be rigid copper pipe. Pipe size to ensure correct operating pressure. For minimum and maximum supply pressure see the System Data table below.

Note: During any pressure testing of the gas supply piping system that exceeds test pressures of 3.45 kPa, this ap- pliance and its individual shut-off valve must be discon- nected from the piping system. If test pressures equal to or less than 3.45 kPa are used then this appliance can be isolated from the piping system by closing its individual manual shut-off valve, if fitted, during the testing.

INSTALLATION IS TO BE CARRIED OUT ONLY BY AN AUTHORISED PERSON

SYSTEM DATA

 

 

NG

LPG

 

Injector size

# 36

# 52

 

 

Input Rating

33 mj

33 mj

 

 

 

 

 

 

Manifold Pressure

0.8 kPa

2.38 kPa

 

 

 

 

 

 

 

 

 

 

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, discon- nect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Screw should be snug, but do not over tighten.

VALVE DESCRIPTION

1)Gas on/off knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection

5)Main Operator

6)Outlet Pressure Tap

7)Inlet Pressure Tap

8)Pilot Outlet

9)Main Gas Outlet

GAS PIPE PRESSURE TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 3.45 kPa. Disconnect piping from valve at pressures over 3.45 kPa.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counter- clockwise with a 1/8" wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

10)Flange Securing Screw Holes

11)Alternative TC Connection Point

12)Thermoelectric Unit

13)Additional Valve Mounting Hole

Regency® F33-3 Freestanding Gas Stove

9

Page 9
Image 9
Regency Wraps F33 Gas Connection, System Data, Valve Description, Gas Pipe Pressure Testing, Installation