RFL NCM RFL Electronics Inc.
November 6, 2007 43 (973) 334-3100
Table 6. Remote configuration settings (“P” codes)
P Code Digit(s) And Switch Equivalent Value (1) Description
P01 B 0 0 0 0 0 0 0 0
- - - - - - -
0 Bus A Disabled
BUS A SETTING
1 Bus A Enabled
B 0 0 0 0 0 0 0 0
- - - - - - -
0 Bus B Disabled
BUS B SETTING
1 Bus B Enabled
B 0 0 0 0 0 0 0 0
- - - - - - -
0 CAS Disabled for E1 MUX
CAS SETTING
(E1 MUX ONLY)
1 CAS Enabled for E1 MUX
B 0 0 0 0 0 0 0 0
- - -
TIMESLOT SELECTION
T1/E1
00001 to 11000
T1 Settings
From left to right, these five bits represent the binary
value of the desired time slot between 1 through 24
in a T1 network. See Table 4 for a complete list of
these values.
00001 to 11111
E1 Settings
From left to right, these five bits represent the binary
value of the desired time slot between 1 through 31
in an E1 network. See Table 4 for a complete list of
these values.
P02 B 0 0 0 0 0 0 0 0
- - - -
From 0000 (0)
to 1001 (9)
BCD Number (0 to 9)
Local CM Address, Hundreds Position
LOCAL CM ADDRESS
(HUNDREDS POSITION)
B 0 0 0 0 0 0 0 0
- - - -
… Not used
P03 B 0 0 0 0 0 0 0 0
- - - -
From 0000 (0)
to 1001 (9)
BCD Number (0 to 9)
Local CM Address, Tens Position
LOCAL CM ADDRESS
(TENS POSITION)
B 0 0 0 0 0 0 0 0
- - - -
From 0000 (0)
to 1001 (9)
BCD Number (0 to 9)
Local CM Address, Units Position
LOCAL CM ADDRESS
(UNITS POSITION)
>> table continues on next page <<
1. These are the only legal values for setting parameters. Setting a parameter to a value outside its specified
range
will produce unpredictable results.