Table 1. - continued, Controls and indicators, RFL NCM Module
Item | Name/Description | Function |
|
|
|
|
|
|
|
| |||
20 | DIP Switch, SW7 | Selects CM address pass setting in NMS application | ||||
|
|
| mode only in accordance with the table below. In all | |||
|
|
| other application modes, these switch settings are | |||
|
|
| ignored. |
|
|
|
|
|
|
|
| ||
|
|
| (ADR1) | (ADR0) | Pass Setting |
|
|
|
| Down | Down | Will pass any messages | |
|
|
|
|
| regardless of the “Local CM | |
|
|
|
|
| Address” setting of the NCM. | |
|
|
|
|
| Messages without address | |
|
|
|
|
| headers are also passed. | |
|
|
| Down | Up | Will only pass messages with | |
|
|
|
|
| addresses equal to the “Local CM | |
|
|
|
|
| Address” setting of the NCM as | |
|
|
|
|
| defined by SW3, SW4 & SW5. | |
|
|
| Up | Down | Will only pass messages with | |
|
|
|
|
| addresses greater than or equal to | |
|
|
|
|
| the “Local CM Address” setting of | |
|
|
|
|
| the NCM as defined by SW3, | |
|
|
|
|
| SW4 & SW5. |
|
|
|
| Up | Up | Will only pass messages with | |
|
|
|
|
| addresses less than or equal to the | |
|
|
|
|
| “Local CM Address” setting of the | |
|
|
|
|
| NCM as defined by SW3, SW4 & | |
|
|
|
|
| SW5. |
|
|
|
|
|
|
|
|
|
| Not Used |
|
|
| |
|
|
| ||||
|
| |||||
|
|
| with the table below: |
| ||
|
|
| Application | |||
|
|
| (Mode 2) | (Mode 1) (Mode 0) | Mode Setting | |
|
|
| Down | Down | Down | broadcast mode |
|
|
| Down | Down | Up | NMS mode |
|
|
| Down | Up | Down | master mode |
|
|
| Down | Up | Up | D&I slave mode |
|
|
| Up | Down | Down | End, slave mode |
|
|
| Up | Down | Up | Undefined |
|
|
| Up | Up | Down | Undefined |
|
|
| Up | Up | Up | Undefined |
|
| Note: Refer to Table 2 for additional switch setting information. | ||||
|
|
|
|
| ||
|
| Enables or disables Port 2 |
| |||
|
|
| UP = Port 2 enabled |
| ||
|
|
| DOWN = Port 2 disabled |
| ||
|
| Note: Port 2 not available when |
| |||
|
|
|
|
| ||
|
| Enables or disables Rogue Control |
| |||
|
|
| UP = Rogue Control enabled |
| ||
|
|
| DOWN = Rogue Control disabled |
| ||
|
|
|
|
|
|
|
21 | DIP Switch, SW8 | Not Used |
|
|
| |
|
|
|
|
|
|
|
22 | DIP Switch, SW9 | Not Used |
|
|
| |
|
|
|
|
|
| |
RFL NCM |
|
|
|
| RFL Electronics Inc. | |
November 6, 2007 | 14 |
|
|