Rheem RMTG-66DV, P), PH-25RDVS, RUTG-66DV, ECO-180DV warranty Horizontal Vent Installation

Models: RMTG-66DV RUTG-66DV ECO-180DV PH-25RDVS P)

1 36
Download 36 pages 8.56 Kb
Page 13
Image 13

Installing the water heater:

Horizontal Vent Installation continued.

 

Inner Wall

 

Outer Wall Plate

 

Inner Wall Plate

94° Elbow

Appliance

Vent

Pipe

Vent Adapter

Outer

 

Wall

 

Caulk for

 

weather seal

 

Water

 

Heater

 

Outside Wall

Mounting

Brackets

Side View

Side View

WARNING: Use UL approved Category III vent material only. No other vent material is permitted.

CAUTION: Follow the vent manufacturer’s installation instructions as design might vary from manufacturer to manufacturer.

Use 4 hollow wall anchors, at least 1/8 inch (0..32 cm) in diameter and of appropriate length for the thickness of the sheathing, if sheathing is particle board or other composite material..

Use 4 #10x1-1/4” wood screws for plywood, solid wood sheathing or members.. Use suitable masonry anchors when passing through solid masonry walls.. Reinstall the decorative sheathing around the faceplate.. This assembly may be painted to match the exterior decor..

Apply silicone sealant or silicone/latex caulk around the vent section where it passes through the plate and around the plate where it is attached to the structure.. This will provide a weather seal to keep moisture outside the building.. Ensure a sufficient seal is made.. Now attach the female end of the air intake tee to the male end of the 3”/5” concentric vent pipe..

Push firmly on the air intake tee until the outer jacket has made contact with the snap ring located on the male end of the 3”/5” concentric vent pipe section.. When fully assembled the outer female end will overlap the male end 1 inch (25..4 mm)..

Use the self-tapping screws provided with the vent kit to connect the two outer pipes..

Seal the over lapping area of the outer pipe (5” concentric pipe) with a thick bead of caulk..

Install the appliance adapter onto the appliance and use (4) four screws to secure the appliance adapter to the appliance.. Now attach other required vent and air intake material between the appliance adapter and the horizontal vent termination..

Maintain the proper clearance between the vent pipe and combustible or non- combustible material as required by the vent manufacturer..

There is a 1" (2..5 cm) minimum clearance required between air intake pipe and combustible or non combustible material..

Proper support be provided for the vent and air intake pipes as mentioned in the venting section..

Support method used should isolate the vent pipe from floor joist or other structural members to help prevent the transmission of noise and vibration..

Do not support, pin, or otherwise secure the venting system in a way that restricts the normal thermal expansion and contraction of the chosen venting material..

7/8" per foot

Wall Plates

downward slope

 

94° Elbow

 

2’

Fire

 

Stop

Vent Pipe

(61 cm)

 

Max .

 

 

 

Ceiling

 

Board

 

Inspection

Inspection

 

Access Panel #1

Access

 

 

Panel #2

Example A: Typical Horizontal Termination

w/ 7/8” per foot DOWNWARD Slope

13

Page 13
Image 13
Rheem RMTG-66DV, P), PH-25RDVS, RUTG-66DV, ECO-180DV warranty Horizontal Vent Installation