Rinnai 26i, HD50i user manual Gas Pressure Setting, mbar

Models: 26i, HD50i

1 40
Download 40 pages 13.22 Kb
Page 30
Image 30
1.9 mbar

GAS PRESSURE SETTING

11.Remove rubber access plug and adjust the regulator screw on the modulating valve (fig. 4) as required to the pressure below. Replace rubber access plug.

N.G

1.9 mbar

 

 

LPG

2.3 mbar

 

 

12.Set the Rinnai Infinity to 'Forced High' combustion by setting no. 7 and no. 8 dipswitches of the top set of switches (SW1) to 'ON'. (fig.5) Ensure maximum water flow.

13.Check the burner test point pressure.

14.Adjust the high pressure potentiometer on the Printed Circuit Board above SW1 (fig. 6) to the pressure shown below. The potentiometer is very sensitive, turn no more than a few degrees at a time; then let the pressure settle down before turning it more.

N.G

8.5 mbar

 

 

LPG

10.8 mbar

 

 

15.IMPORTANT: Set dip switch no. 7 and no. 8 on the top set of switches (SW1) to 'OFF'

to return the appliance to 'Normal' combustion.

16.Close hot water tap.

17.Turn OFF the gas supply and 230V power supply.

18.Remove pressure gauge, and replace sealing screw

19.Turn 'ON' the gas supply and 230V power supply.

20.Operate unit and check for gas leaks at test point.

21.Replace the front cover of the appliance.

off on SW1 1 2 3 4 5 6 7 8

fig. 5

High Press.

Potentiometer

fig. 6

CAUTION

30

Page 30
Image 30
Rinnai 26i, HD50i user manual Gas Pressure Setting, mbar