GAS PRESSURE SETTING

GAS PRESSURE SETTING

The working gas pressure on the water heater is electronically controlled and factory set. Under normal circumstances it does not require adjustment during installation. Perform this procedure only if the unit is not operating correctly and all other possible causes for incorrect operation have been eliminated. Contact Rinnai UK before

attempting to alter the gas pressure. Failure to do so could void the warranty.

1.Turn 'OFF' the gas supply.

2.Turn 'OFF' 230V power supply.

3.Remove the front cover from the appliance.

4.Check gas type switch no.1 of SW2 is in the correct position for the type of gas (Nat. or LPG) you are using. (SW2 is bottom set of switches.)

off on SW2

 

off on SW2

 

 

 

1

-Nat. Gas

 

 

1

-LPG

 

 

2

 

 

 

2

 

 

 

3

 

 

 

3

 

 

 

4

 

 

 

4

 

*On is in the forward position, Off is in the back position. Pull the switch toward you to put it in the on position.

5.Attach pressure gauge to burner test point. (fig. 2)

6.Turn 'ON' the gas supply.

7.Turn 'ON' 230V power supply.

8.If remote controllers are fitted, turn the unit 'ON' at the master controller, select a maximum delivery temperature and open a hot water tap fully. (CAUTION: Ensure building occupants do not have access to hot water outlets during this procedure.)

9.Set the Rinnai Infinity to 'Forced Low' combustion by setting No. 7 dipswitch of the top set of dip switches (SW1) to 'ON'. (fig 3)

10.Check the burner test point operating pressure.