Flue Installation (R98LSi, R98LSi-ASME)

Flue Installation (R98LSi, R98LSi-ASME)

Air Intake Assembly

1

2

The air intake system consists of a field supplied 4 inch diameter stainless steel, Schedule 40 PVC, ABS or CPVC pipe. A maximum 6 feet of semi-rigid flexible aluminum ducting can also be used. Foil wrapped dryer vent and cell core products are not authorized.

The air intake has a zero clearance to combustibles.

Air Intake Connection

3

4

1. Drill 2 small holes at the end of the air intake

pipe.

 

 

2.Slide the pipe over the air intake terminal.

3.Using a level, ensure the pipe is straight up and down.

4.With self tapping screws, attach the pipe to the air intake terminal.

5.Apply a bead of silicone around the pipe and air intake terminal, ensuring an air tight connection.

Exhaust Pipe Assembly

Refer to the manufacturer’s installation instructions for the specific exhaust vent system.

Venting Clearances to Combustibles

 

Enclosed

Unenclosed

Vent Size

 

 

Horizontal &

Horizontal &

 

Vertical

Vertical

4" (102 mm)

4" (102 mm)

1" (26 mm)

 

 

 

Horizontal Terminations

The air intake must be located in relation to the exhaust as shown below. The air intake must angle 1/4 inch per foot to the termination to prevent entry of rain.

6

Vent

8

Optional

Intake

Intake

The vent termination and air intake must be in the same pressure zone and face the same direction.

EXHAUSTAir Intake Assembly

COMBUSTION AIR /

INTAKE Exhaust Pipe Assembly

SLOPE INTAKE AND EXHAUST

TOWARD OUTSIDE TERMINATION

MINIMUM 1/4" PER FOOT

 

 

 

 

 

 

 

 

 

 

 

 