CTH2-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 8: VENTING

WARNING

Carbon Monoxide Hazard

Heaters installed unvented must be interlocked with sufficient building exhaust.

Heaters must be installed according to the installation manual.

Failure to follow these instructions can result in death or injury.

WARNING

Cut/Pinch Hazard

Wear protective gear during installation, operation and service.

Edges are sharp.

Failure to follow these instructions can result in injury.

8.1 General Venting Requirements

This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply:

United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.

Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.

Exhaust end of heater will accept a 4' (10 cm) vent pipe using the vent adapter (P/N 90502700). To prevent leakage of condensation, install the vent adapter with the seam on top and seal the joint using a high temperature silicone sealant.

Any portion of vent pipe passing through a combustible wall must have an approved thimble to conform with the above listed codes.

Vent pipe must be sloped downward away from the burner 1/2'' (1 cm) for every 20' (6 m).

The heater may be individually vented or common vented. When venting horizontally, a maximum of two heaters can be commonly vented. See Page 36, Section 8.9. When venting vertically, a maximum of four heaters can be commonly vented. See Page 37, Section 8.10.

The heater may also be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 34, Section 8.2 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 8, Figure 12.

The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.

The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.

Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.

Secure all joints with #8 x 3/8 sheet metal screws. Seal all joints with high temperature silicone sealant.

Vent terminal must be beyond any combustible overhang.

8.1.1 United States Requirements

Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).

Vent must terminate at least 4' (1.2 m) below, 4'

(1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.

8.1.2 Canadian Requirements

The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.

The vent shall not terminate within 3' (.9 m) of a

window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.

8.2 Unvented Operation

Sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).

Use of optional outside combustion air is not recommended with unvented heaters.

If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a pressure switch.

34

Page 40
Image 40
Roberts Gorden CTH2-175, CTH2-125, CTH2-80 General Venting Requirements, United States Requirements, Canadian Requirements

CTH2-40 CTH2-60, CTH2-175, CTH2-150, CTH2-100, CTH2-80 specifications

Roberts Gorden is a reputable name in the field of heating and energy efficiency, and its CTH2 series of infrared radiant heaters—including the CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175—are a testament to innovation and quality. Designed for commercial and industrial spaces, these heaters provide effective and efficient heating solutions tailored to various needs.

The CTH2 series employs advanced infrared heating technology, which radiates warmth directly to objects and individuals in the space rather than heating the air. This method ensures rapid heat-up times and energy conservation, making the heaters ideal for workshops, warehouses, and other large areas where traditional heating systems may be inefficient.

One of the main features of the CTH2 series is its high thermal efficiency. The heaters convert a significant portion of the energy consumed into usable heat, resulting in lower operational costs and a reduced carbon footprint. The CTH2 models utilize durable components designed to withstand the rigors of industrial environments, ensuring longevity and reliable performance.

The CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175 models vary in output capacity and design, providing flexibility for different heating requirements. The maximum heat output ranges significantly among the models, with the CTH2-175 offering the highest thermal output, making it suitable for larger spaces or areas requiring immediate and intense heating. Conversely, the CTH2-80 is ideal for smaller areas or those that require less heat.

Installation versatility is another key characteristic of the CTH2 series. These heaters can be mounted from the ceiling or installed horizontally or vertically, accommodating different building layouts and operational needs. The heaters are also designed for easy maintenance, featuring accessible components to facilitate routine checks and repairs.

The CTH2 series incorporates safety features such as overheat protection and flame safeguard systems, ensuring safe operation even in busy industrial settings. Additionally, their sleek and modern design allows them to integrate seamlessly with existing infrastructure without detracting from the overall aesthetic of the space.

In conclusion, Roberts Gorden’s CTH2 series—including the CTH2-150, CTH2-80, CTH2-125, CTH2-100, and CTH2-175—represents a pinnacle of infrared heating technology. With their impressive efficiency, customizable output, versatile installation options, and robust safety features, these heaters are a reliable choice for any commercial or industrial heating requirement.