![SECTION 14: GENERAL SPECIFICATIONS](/images/new-backgrounds/34890/34890123x1.webp)
SECTION 14: GENERAL SPECIFICATIONS
14.1Material Specifications 14.1.1 Reflectors
.024 Aluminum
(optional .024 Stainless Steel Type 304)
14.2Heater Specifications 14.2.1 Ignition
Honeywell® SmartValve® II combines gas valve and hot surface electronic ignition control. Fully auto- matic,
14.3 Suspension Specifications
Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 14, Figure 14.
14.4 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.
General Specifications for the heaters are as follows:
End View | Side View |
| Minimum Length "A" | |
|
| Reflector | ||
|
|
|
| |
13.5" |
|
|
|
|
(34 cm) |
|
|
|
|
9.5" |
|
|
|
|
(24 cm) |
|
|
|
|
| 17.5" | Burner Tube | Turbulator | |
|
| (Select Models) | ||
| (44 cm) |
|
|
|
| Heat Input Rate | Length “A” | Recommended | |
| Minimum Mounting Height* | |||
|
|
| ||
Model | (Btu/h) x (1000) | Minimum | Space | Spot |
40 | 10' (3m) | 8' (2.3m) | ||
60 | 20' (6m) | 9' (2.7m)' | ||
80 | 20' (6m) | 11' (3.3m) | ||
100 | 30' (9m) | 12' (3.7m) | ||
125 | 40' (12m) | 15' (4.6m) | ||
150 | 50' (15m) | 20' (6.1m) | ||
175 | 60' (15m) | 25' (7.6m) | 23' (7m) |
*See Page 5, Section 3 for clearances to combustibles.
GAS PRESSURE AT MANIFOLD:
Natural Gas: | 3.5" wc |
LP Gas: | 10.5" wc |
PIPE CONNECTION:
1/2" NPT (for 40, 60, 80, 100, 125) 3/4" NPT (for 150 & 175)
DIMENSIONS:
Vent Connection Size: 4" (10 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.
GAS INLET PRESSURE: |
|
|
Natural Gas: |
|
|
for 40,60,80,100,125,150 | 4.6" wc | Minimum |
for 175 | 5.0" wc | Minimum |
| 14.0" wc | Maximum |
LP Gas: | 11.0" wc | Minimum |
| 14.0" wc | Maximum |
ELECTRICAL RATING (ALL MODELS):
120 V - 60 Hz., 1.0 A (run) 5.0 A (Start)
56