Roberts Gorden Linear Heater General Specifications, Material Specifications 14.1.1 Reflectors

Models: Linear Heater

1 50
Download 50 pages 4.35 Kb
Page 44
Image 44
SECTION 14: GENERAL SPECIFICATIONS
14.3 Suspension Specifications
Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 14, Figure 14.
14.4 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 14: GENERAL SPECIFICATIONS

14.1 Material Specifications

14.1.1 Reflectors

.024 Aluminum

(Optional .024 Stainless Steel Type 304)

14.2 Heater Specifications

14.2.1 Ignition

Fully automatic spark ignition with safety shut-off.

General Specifications for BH-Series heaters are as follows:

End View

Side View

 

Reflector

 

 

 

 

 

 

 

 

 

12.5"

 

 

 

 

Turbulator (select models)

(32 cm)

 

 

 

 

 

 

 

 

 

 

12.5"

 

 

Burner Tube

Minimum Length A

 

 

11"

 

 

 

 

(32 cm)

 

 

 

 

 

(28 cm)

 

 

 

 

 

 

 

 

 

 

 

 

Heat Input Rate

Length “A”

Recommended

 

 

Minimum Mounting Height*

 

 

 

 

Model

(Btu/h) x (1000)

Minimum

Space

Spot

BH-40

40

10' (3 m)

8-10' (2.4 - 3 m)

8'(2.4 m)

BH-60

60

20' (6 m)

10-12' (3 - 3.6 m)

9' (2.7 m)

BH-80

80

20' (6 m)

12-15' (3.6 - 4.5 m)

11'

(3.3 m)

BH-100

100

30' (9 m)

12-15' (3.6 - 4.5 m)

12'

(3.7 m)

BH-115

115

30' (9 m)

15-20' (4.5 - 6 m)

15'

(4.6 m)

BH-125

125

40'

(12 m)

15-20' (4.5 - 6 m)

15'

(4.6 m)

BH-140

140

40'

(12 m)

20-25' (6 - 7.6 m)

20'

(6.1 m)

BH-150

150

50'

(15 m)

20-25' (6 - 7.6 m)

20'

(6.1 m)

BH-175

175

50'

(15 m)

25' (7.6 m)

23' (7 m)

BH-200

200

60'

(18 m)

25' (7.6 m)

25'

(7.6 m)

*See Page 4, Section 3 for clearances to combustibles.

GAS PRESSURE AT MANIFOLD:

Natural Gas:

3.5" wc

LP Gas:

10.5" wc

PIPE CONNECTION:

1/2" NPT (for BH-40, 60, 80, 100, 115 & 125) 3/4" NPT (for BH- 140, 150,175 & 200)

DIMENSIONS:

Vent Connection Size: 4" (10 cm)

Outside Air Connection Size: 4" (10 cm)

Refer to figure above for dimensional information.

GAS INLET PRESSURE:

 

 

Natural Gas:

 

 

for BH-40, 60, 80, 100,

 

 

115, 125, 140, 150

4.6" wc Minimum

for BH-175, 200

5.0" wc

Minimum

 

14.0" wc

Maximum

LP Gas:

11.0" wc

Minimum

 

14.0" wc Maximum

ELECTRICAL RATING (ALL MODELS):

120 V - 60 Hz, 1 A