ROBERTS GORDON® ULTRAVAC™ CONTROLLER INSTALLATION MANUAL
FIGURE 12: ROBERTS GORDON® ULTRAVAC™ Satellite Controller External Wiring
| To Satellite Controller | |
| ||
Zone 1 | (See NOTE 2) | |
Zone 2 | ||
Sensor | Sensor | |
(see NOTE 6) | (see NOTE 6) |
|
SEN SET O/R - + | SEN SET O/R - + |
NC C NO
BMS Enable
(optional)
NC C
NCNO
C NO
NC C
NO NC
C NO
-
+8
- 7 +
- +6 UNIVERSAL - 5 +
- +4
- 3 INPUTS +
- 2 +
| - |
|
|
|
| +1 |
|
|
|
OFF ON | OUT IN | CPU | ADDRESS | RESET |
10VDC | 499 OHM |
|
| OH |
CD RI
|
| NC C NO NC C NO NC C NO NC C NO |
| L2 L1 PWR 24VAC | |
RS232 DIRECT |
| OUT IN G |
AUX |
| +32 +5 |
POWER |
| G |
|
| G |
|
| G |
RS485 | OUT | REF |
| - | |
| + | |
COMM |
| REF |
+ | ||
| - | |
| IN |
|
| - |
| |
| 4 |
| |
METER | + |
| |
+ |
| ||
| - |
| |
INPUTS | 3 |
| |
+- |
| ||
| - |
| |
| 2 |
| |
| 1 |
| |
| + |
| |
|
|
|
|
Join Shields - Do Not Ground
OUTPUT 8 | L1 L2 GRD |
OUTPUT 7 | L1 L2 GRD |
OUTPUT 6 | L1 L2 GRD |
OUTPUT 5 | L1 L2 GRD |
OUTPUT 4 | L1 L2 GRD |
OUTPUT 3 | L1 L2 GRD |
OUTPUT 2 | L1 L2 GRD |
OUTPUT 1 | L1 L2 GRD |
POWER | L2 GRD |
| L1 |
Continued
On Next
Page
(See NOTE 2)
Electrical wiring connections indicated by a dot;
Ground Shield (one end only) indicated by;
Separate line and low voltage circuits.
Do not run line voltage wiring through bottom section of enclosure that houses the control board. Do not run low voltage wiring through top section of enclosure that houses the relay board.
Do not run line and low voltage wiring in the same conduit.
NOTE 1: This diagram applies to the Satellite Controller only.
The Satellite Controller does not require modem,
120 V
1 Ø
From previous 60 Hz controller
(See NOTE 2)
Pressure
Switch (Pump)
Pressure Switch
(Optional Outside Air Blower)
TCP/IP module wiring, or outdoor sensor wiring.
NOTE 2: Twist shield wires for both
NOTE 3: 120 V 1 Ø
supply for 460 V VFD model. See VFD rating plate for required input. Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive.
NOTE 4: Zone 3 Sensor(not shown) wiring is as follows: SEN output to analog input 3; SET output to analog input 6; O/R output to meter input 3; +/- outputs to +32 V/GND inputs.
NOTE 5: Internal
NOTE 6: Wiring from 32 V terminals on the controller to sensor power terminals "+" and
NOTE 7: All three power output wires from terminals U, V, and W to the pump motor must be kept tightly bundled and run in a separate conduit away from all other power and control wiring.
18