Roberts Gorden NEMA 4 installation manual

Models: NEMA 4

1 48
Download 48 pages 39.44 Kb
Page 31
Image 31
If more than one ROBERTS GORDON® ULTRA- VAC™ Controller is installed in a building, the controllers’ RS-485 communications must be wired in series. See Page 25, Figure 18. Connect the RS-485 terminal on controller #1 to the RS-485 terminal on controller #2 and so on in a daisy chain fashion. For communication cable requirements, See Page 12, Section 3.3.5

SECTION 5: COMMUNICATIONS

5.5 Communications Between Multiple ROBERTS GORDON® ULTRAVAC™ Controllers

If more than one ROBERTS GORDON® ULTRA- VAC™ Controller is installed in a building, the controllers’ RS-485 communications must be wired in series. See Page 25, Figure 18. Connect the RS-485 terminal on controller #1 to the RS-485 terminal on controller #2 and so on in a daisy chain fashion. For communication cable requirements, See Page 12, Section 3.3.5

From a PC, by dialing into the modem on controller #1 or by connecting to controller #1 via RS-485 converter or TCP/IP communication module, the

system status and settings can be viewed for any of the controllers on the network.

The control board identification dip switch must be set on each ROBERTS GORDON® ULTRAVAC™ Controller. See Page 25, Figure 18 for dip switch settings. Contact Roberts-Gordon or your ROBERTS GORDON® independent distributor, if more than 20 controllers are connected.

FIGURE 18: Communications Between Multiple Controllers

Central Controller

(controller #1)

RS 485

Satellite Controller

(controller #2)

Satellite Controller

(controller #3)

To Additional Controllers

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

-

8

+

 

-

7

+

 

-

6

+ - +

UNIVERSAL 5

-

INPUTS 4

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

24VAC

L2 L1

 

PWR

RS232 DIRECT

OUT IN

 

G

AUX

+32 +5

 

G

Wiring

To RJ11

connection on

TCP/IP

Module

(optional)

Ground

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

-

8

+

 

-

7

+

 

-

6

+ - +

UNIVERSAL 5

-

INPUTS 4

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

24VAC

L2 L1

 

PWR

RS232 DIRECT

OUT IN

 

G

AUX

+32 +5

 

G

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

-

8

+

 

-

7

+

 

-

6

+ - +

UNIVERSAL 5

+ -

INPUTS 4

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

 

NC

 

C

 

NO

24VAC

L2 L1

 

PWR

RS232 DIRECT

OUT IN

 

G

AUX

+32 +5

 

G

Join Shields - Do Not Ground

Dedicated

Outside

Phone Line

(optional)

 

+

 

 

-

 

 

3

 

+

 

 

-

 

 

2

 

+

 

 

-

 

 

1

 

+

 

OFF ON

OUT IN

CPU

ADDRESS

RESET

10VDC

499 OHM

 

 

OH

 

 

 

 

CD

 

 

 

 

RI

POWER

 

G

 

 

 

 

G

 

 

 

 

 

 

RS485

OUT

+-REF

 

 

 

 

COMM

IN

-REF

 

 

 

 

+

 

 

 

 

 

 

 

4

-

 

 

 

+

 

 

 

 

 

 

METER

3

+ -

 

 

INPUTS

2

+ -

 

 

 

1

-

 

 

 

+

 

 

 

 

 

 

 

 

 

 

Shield

Wiring

to RS 485 Converter at PC (optional)

 

+

 

 

-

 

 

3

 

+

 

 

-

 

 

2

 

+

 

 

-

 

 

1

 

+

 

OFF ON

OUT IN

CPU

ADDRESS

RESET

10VDC

499 OHM

 

 

OH

 

 

 

 

CD

 

 

 

 

RI

 

POWER

 

G

 

 

 

G

 

 

 

 

 

RS485

OUT

+-REF

 

COMM

IN

-REF

 

 

 

+

 

 

 

 

 

 

4

-

 

 

+

 

 

 

 

METER

3

+ -

 

INPUTS

2

+ -

 

 

1

-

 

 

+

 

 

 

 

 

 

 

 

 

 

 

Join Shields - Manual background Do Not Ground

 

-

 

3

 

+

 

-

 

2

 

+

 

-

 

1

 

+

OFF ON

OUT IN

10VDC

499 OHM

CPU

ADDRESS

RESET

 

 

OH

 

 

CD

 

 

RI

POWER

 

G

 

 

G

RS485

OUT

+-REF

COMM

IN

-REF

 

 

+

 

4

-

 

+

 

 

METER

3

+ -

INPUTS

2

+ -

 

1

-

 

+

 

 

1 2 3 4 5 6 7 8Manual backgroundManual backgroundManual backgroundManual background

Manual background ModemManual background

Chip

Dip Switch #1

Set to ON (controller address #1)

1 2 3 4 5 6 7 8Manual backgroundManual backgroundManual backgroundManual background

Dip Switch #2

Set to ON (controller address #2)

1 2 3 4 5 6 7 8Manual backgroundManual backgroundManual backgroundManual background

Dip Switch

#1 and #2 Set to ON (controller address #3)

 

 

 

 

 

 

Controller

Dip

Switch Order

(1,2,3,4,5,6,7,8)

 

Number

 

Values (1=ON, 0=OFF)

 

 

 

1 (Central Controller)

10000000

 

 

 

 

2

01000000

 

 

 

 

3

11000000

 

 

 

 

4

00100000

 

 

 

 

5

10100000

 

 

 

 

6

01100000

 

 

 

 

7

11100000

 

 

 

 

8

00010000

 

 

 

 

9

10010000

 

 

 

 

10

01010000

 

 

 

 

 

 

 

 

 

 

 

Controller

 

Dip Switch

Order (1,2,3,4,5,6,7,8)

Number

Values (1=ON, 0=OFF)

 

 

 

11

 

11010000

 

 

 

12

 

00110000

 

 

 

13

 

10110000

 

 

 

14

 

01110000

 

 

 

15

 

11110000

 

 

 

16

 

00001000

 

 

 

17

 

10001000

 

 

 

18

 

01001000

 

 

 

19

 

11001000

 

 

 

20

 

00101000

 

 

 

 

25

Page 31
Image 31
Roberts Gorden NEMA 4 installation manual