ROBERTS GORDON® ULTRAVAC™ CONTROLLER INSTALLATION MANUAL
FIGURE 11: ROBERTS GORDON® ULTRAVAC™ Central Controller External Wiring
To Satellite Controller
(see NOTE 2)
Zone 1 | Zone 2 | Outdoor |
Sensor | Sensor | |
(see NOTE 6) | (see NOTE 6) | Sensor |
SEN SET O/R - + | SEN SET O/R - + |
|
|
| + - |
NC C NO
BMS Enable
(optional)
Phone Line
for Modem
(optional)
(see NOTE 1)
NC C NO NC C NO NC C NO NC C NO |
| ||
- | 8 |
| |
+ |
|
| |
- | 7 |
| |
+ |
| ||
6 5 | UNIVERSAL | ||
+ | |||
- |
|
| |
+ |
|
| |
- | 43 | INPUTS | |
- | |||
- |
|
| |
+ |
|
| |
+ |
|
| |
- | 2 |
| |
+ |
|
| |
- | 1 |
| |
+ |
|
|
OFF ON | OUT IN | CPU | ADDRESS | RESET |
10VDC | 499 OHM |
|
| OH |
CD RI
1 | 2 | 3 | 4 |
+ - | + - | + - | + - |
|
|
|
|
|
|
|
|
(See
NOTE 2)
|
| NC C NO NC C NO NC C NO NC C NO |
| 24VAC | L2 L1 PWR |
RS232 DIRECT |
| OUT IN G |
AUX POWER |
| +32 +5 G G G |
RS485 |
| REF |
| + | |
| OUT | |
|
| - |
COMM |
| REF |
IN | ||
|
| - |
|
| + |
|
| - |
|
|
| 4 |
|
METER | + |
| |
+ |
| ||
|
| - |
|
INPUTS | 3 |
| |
+- |
| ||
|
| - |
|
|
| 2 |
|
|
| 1 |
|
|
| + |
|
|
|
|
|
OUTPUT 8 | L1 L2 GRD |
| |
OUTPUT 7 | L1 L2 GRD |
| |
OUTPUT 6 | L1 L2 GRD |
| |
OUTPUT5 | L1L2 GRD |
| |
| Continued | ||
OUTPUT4 | L2L1GRD | On Next | |
Page | |||
|
| ||
OUTPUT 3 | L1 L2 GRD |
| |
OUTPUT 2 | L1 L2 GRD |
| |
OUTPUT 1 | L1 L2 GRD |
| |
POWER | L2 GRD |
| |
| L1 |
| |
| 120 V |
| |
| 1 Ø |
| |
To | 60 Hz |
| |
Converter at PC |
|
|
(optional)
(see NOTE 1 & 2)
Electrical wiring connections indicated by a dot;
Ground Shield (one end only) indicated by;
Separate line and low voltage circuits.
Do not run line voltage wiring through bottom section of enclosure that houses the control board. Do not run low voltage wiring through top section of enclosure that houses the relay board.
Do not run line and low voltage wiring in the same conduit.
Pressure
Switch (Pump)
Pressure Switch
(Optional Outside Air Blower)
NOTE 1: This diagram applies to the Central
Controller (controller #1) only. For all Satellite Controllers see Satellite Controller External Wiring Diagram. Central Controller (controller #1) requires outdoor sensor wiring and either modem,
NOTE 2: Twist shield wires for both
NOTE 3: 120 V 1 Ø
(more than once every two minutes) may cause damage to the drive.
NOTE 4: Zone 3 Sensor(not shown) wiring is as follows: SEN output to analog input 3; SET output to analog input 6; O/R output to meter input 3; +/- outputs to +32 V/GND inputs.
NOTE 5: Internal
NOTE 6: Wiring from 32 V terminals on the controller to sensor power terminals "+" and
NOTE 7: All three power output wires from terminals U, V, and W to the pump motor must be kept tightly bundled and run in a separate conduit away from all other power and control wiring.
16